| 2001-09-14 00:00:00 | FAILED: |
| | 1. PLEASE SPECIFY THE THICKNESS OF THE |
| | SUBGARADE FOR PROPOSED DRIVEWAYS AND |
| | PARKING AREA. |
| | 2. PLEASE SHOW DETAILS FOR THE PATTERNED |
| | CONCRETE AREA AND SLAB ON GRADE IN |
| | APPARATUS BAY AREA OR REFER TO |
| | APPROPRIATE SHEET FOR DETAILS. |
| | 2. PLEASE REVISE THE PARKING SPACE |
| | STRIPING DETAIL TO COMPLY WITH CITY'S |
| | REQUIREMENTS, ALL OFF- STREET PARKING |
| | SPACES MUST BE PAINTED WITH DOUBLE 4" |
| | WHITE FOR REGULAR AND BLUE FOR |
| | H.C PARKINGS. |
| | 3. PLEASE SPECIFY SIZE FOR THE OIL/WATER |
| | SEPARATOR AND SHOW CONNECTION TO THE |
| | TRENCH DRAINS ( PLUMBING PLANS ), CALL |
| | RODNEY COMPO FOR INSTALLATION/INSPECTION |
| | AT 837-4051 EXT. 4074. |
| | 4. PLEASE PROVIDE DETAILS FOR THE |
| | PROPOSED DUMPSTER, REFER TO PREVIOUS |
| | REVIEW COMMENTS FOR THE REQUIREMENTS. |
| | 5. PLEASE PROVIDE LANDSCAPING AND |
| | IRRIGATION PLANS. |
| | 6. SHEET 5 OF 17, SANITARY SEWER PROFILE |
| | SHOWS THAT 8" PVC SAN. IS CONNECTED TO |
| | EXISTING MH AT INV. 10.0 AND 8" PVC |
| | LEAVING AT INV. 4.5W, IS THE EXISTING |
| | MH A DROP MH ? |
| | 7. PLEASE PROVIDE DETAILS FOR THE |
| | STRIP DRAINAND SPICIFY THE SIZE OF THE |
| | RCP CONNECTING TO THE PROPOSED TYPE C |
| | INLET. |
| | 8. ALL PLANS AND CALCULATIONS SUBMITTED |
| | FOR PERMITTING MUST BE SIGNED AND SEALED |
| | BY THE DESIGN ENGINEERS AT THE TIME FOR |
| | ACTUAL PERMITTING. |
| | |
| | IF ANY QUESTIONS PLEASE CONTACT 659-8096 |
| | EXT. 8492 MOHAMMAD R. AMINI |