Plan Review Notes
Plan Review Notes For Permit 01070541
Permit Number 01070541
Review Stop ENG
Sequence Number 2
Notes
Date Text
2001-09-14 00:00:00FAILED:
 1. PLEASE SPECIFY THE THICKNESS OF THE
 SUBGARADE FOR PROPOSED DRIVEWAYS AND
 PARKING AREA.
 2. PLEASE SHOW DETAILS FOR THE PATTERNED
 CONCRETE AREA AND SLAB ON GRADE IN
 APPARATUS BAY AREA OR REFER TO
 APPROPRIATE SHEET FOR DETAILS.
 2. PLEASE REVISE THE PARKING SPACE
 STRIPING DETAIL TO COMPLY WITH CITY'S
 REQUIREMENTS, ALL OFF- STREET PARKING
 SPACES MUST BE PAINTED WITH DOUBLE 4"
 WHITE FOR REGULAR AND BLUE FOR
 H.C PARKINGS.
 3. PLEASE SPECIFY SIZE FOR THE OIL/WATER
 SEPARATOR AND SHOW CONNECTION TO THE
 TRENCH DRAINS ( PLUMBING PLANS ), CALL
 RODNEY COMPO FOR INSTALLATION/INSPECTION
 AT 837-4051 EXT. 4074.
 4. PLEASE PROVIDE DETAILS FOR THE
 PROPOSED DUMPSTER, REFER TO PREVIOUS
 REVIEW COMMENTS FOR THE REQUIREMENTS.
 5. PLEASE PROVIDE LANDSCAPING AND
 IRRIGATION PLANS.
 6. SHEET 5 OF 17, SANITARY SEWER PROFILE
 SHOWS THAT 8" PVC SAN. IS CONNECTED TO
 EXISTING MH AT INV. 10.0 AND 8" PVC
 LEAVING AT INV. 4.5W, IS THE EXISTING
 MH A DROP MH ?
 7. PLEASE PROVIDE DETAILS FOR THE
 STRIP DRAINAND SPICIFY THE SIZE OF THE
 RCP CONNECTING TO THE PROPOSED TYPE C
 INLET.
 8. ALL PLANS AND CALCULATIONS SUBMITTED
 FOR PERMITTING MUST BE SIGNED AND SEALED
 BY THE DESIGN ENGINEERS AT THE TIME FOR
 ACTUAL PERMITTING.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI