2001-09-17 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070541
 4301 S DIXIE HWY
 PLAN CHECK: 01070541
  
 SBC= STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 TYPE V UNPROTECTED / SPRINKLERED
  
 1)- STAT STATUTE 481 ARCHETECTURAL
 DRAWINGS SUBJECT TO PUBLIC RECORD ARE
 TO BE SIGNED,SEALED & DATED.
  
 2)- SBC 104.2.2* A SSURVEY LESS THAN A
 YEAR OLD.
  
 3)- SBC 1804.2.2* SOILS REPORT, MINIMUM
 BEARING VALUE
  
 4)- FL ENERGY CODE, ENERGY CALCULATIONS.
  
 5)- FIRE DISTRICT F-102.4 ROOF COVERINGS
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS"A" OR "B" ROOF COVERINGS.
  
 6)- SHEET A4.2 DETAIL #4 (FOAM) F 102.7
 ARCHITECTURAL TRIM ON BUILDINGS IN A
 FIRE DISTRICTSHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.
  
 ASCE 7-98 PRODUCT APPROVALS BASED ON
 145 MPH / 3 SEC. GUST
 7)- COMPONEMNTS & CLADDING
 THE CITY WILL REQUIRE PRODUCT TESTING
 RREPORTS (2 COPIES ) FOR THEFOLLOWING
 ITEMS:
 A- DOORS
 B- OVERHEAD GARAGE DOORS
 C- SLIDING GLASS DOORS
 D- WINDOWS
 E- GLASS BLOCK
 F-SKYLIGHTS
 G- ROOFING MATERIALS & ROOF TILE
  
 ALL WALL OPENINGS (DOORS & WINDOWS) WILL
 REQUIRE THE POSITIVE / NEGATIVE PRESSURE
 THAT WILL BE APPLIED, IMPORTANCE FACTOR,
 WALL & END ZONES ARE TO BE FACTORED INTO
 THE OPENINGS. SEE CITY INTERPRETATION
 FOR LARGE MISSLE IMPACT RESISTANCE FOR
 GLAZED OPENINGS.
  
 WINDOW / SHUTTER ARE TO SHOW PRODUCT
 TESTING AS THET ARE BEING INSTALLED IN
 THIS TYPE INSTALATION. SHEET A8.4/1.
  
 8)- PLANS ARE TO NOTE: FL ACCES CODE
 4.3.6/ 4.5.1 GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES AND IN ACCESS-
 IBLE ROOMS & SPACES INCLUDING FLOORS,
 WALKS, RAMPS, STAIRS & CURBS SHALL BE
 STABLE, FIRM, SLIP RESISTANT. ADDAAG A-5
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.A8.1 ROOM FINISH SCH.
  
 9)- STRUCTURAL PLANS SBC 104.2.2*
 ADDITIONAL INFORMATION REQUIRED, MISSING
 IS INFORMATION, FOOTINGS, THE SCHEDULE
 IS THERE BUT NO MARK INDICATION ON S2.1.
 THE SAME FOLLOWS TRUE FOR THE COLUMNS &
 BEAMS.NO HOOPS!!!!!
 THE TRUSS PLAN MISSING THE MEAN ROOF
 HEIGTH, DESIGN INFO, TRUSS AND GIRDER
 LOADS VERTICAL, HORIZONTAL & GRAVITY
 LOADING. SPECIAL ROOF SHEATHING NAILING
 ZONES.
  
 10)- WINDOW BUCK DETAIL SHEET A8.4
 DETAIL #2, 1/2" TAPCONS W/ 4" EMBEDMENT
 IS 1/2" A MISPRINT?
  
 11)- SHEET A8.4 SEC 7 GLASS BLOCK,
 CITY INTERPRETATION GLASS BLOCK TO COMPL
 Y WITH SBC 2112 TO BE EXEMPT FROM STORM
 SHUTTERS. SHOW PRODUCT TESTING.
  
 12)- SHEET A2.3 NO DIMENSIONS
  
 13)- A8.3 DETAILS 10, 11 1/2" EXPANSION
 BOLTS NO SPACING OR MIN. EMBEDMENT.
  
 14)- SBC 1517.1.2.1. TOWERS OVER 25' AND
 OVER 200' HORIZONTALLY 14.66'X 15.33'=
 224.73'
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412