Plan Review Notes
Plan Review Notes For Permit 01070541
Permit Number 01070541
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-12 00:00:00PLUMBING PLAN REVIEW, DENIED.
 CODE REFERENCES SPC-94,SGC-97, FACBC-97
 (1) SHT-2,SITE PLAN: GREASE TRAP TO BE
 SIZED BY WPB REGIONAL SEWER PLANT.
 CONTACT RODNEY COMPO 561-837-4074.
 (2) ALL SITE UTILITIES, 5'OUTSIDE OF THE
 BUILDING,TO COMPLY WITH CITY OF WPB UTIL
 ITIES STDS, SEE ENGINEERING COMMENTS.
 (3) SHT P2-1 PARK REST RM'S #141,#142
 COMPLY W/FACBC SEC 4.22 ACCESSIBLE
 TOILET RM'S,TURNING RADIUS,CLEAR FLOOR
 SPACE SEC 4.22.5
 D/F SEC 4.1.3(10)(A) CUP DISPENSER FOR
 THOSE WHO HAVE TROUBLE BENDING OR
 STOOPING.OR USE A HIGH LOW D/F.
 (4) FLOOR DRAINS IN PUBLIC REST RM'S,
 SEC 409.4, MIN SIZE 3", W/TRAP PRIMER.
 (5) PUBLIC TOILET RM #112,COMPLY W/SEC.
 4.22, ACCESSIBLE TOILET RM'S FOR PUBLIC.
 (6) RM #111 PANTRY (BREAK RM) SINK TO
 COMPLY W/ SEC 4.24.1 ACCESSIBLE,HEIGHT
 SEC 4.24.2,CLEAR FLR SPACE,SEC 4.24.5
 (7) TOILET RM #124, PRIVATE TOILET RM
 TO BE ADAPTABLE, SEC 4.1.3(11).
 SHOWER SEC 4.21,SIZE,SEAT,CURB,GRAB BARS
 CONTROLS.
 (8) DORM REST RM'S #118,#132 COMPLY WITH
 SEC 4.22, ACCESSIBLE TOILET RM'S, CLEAR
 FLOOR SPACE.SHOWER STALL.SEC 4.21 SIZE
 SEAT,CURB,GRAB BARS,CONTROLS.
 (9) KITCHEN: RM #135, ALL INDIRECT WASTE
 TO FLR SINKS\\, (ICE MACHINE)
 (10) KITCHEN: RM #135,SEE ATTACHED GAS
 PERMIT APPLICATION REQUIRMENTS,ADDRESS
 EA COMMENT CIRCLED (13),SEPERATE PERMIT
 REQUIRED.
 (11) COMPLY W/SEC 104.3,PLANS: PROVIDE
 AN ISOMETRIC DRAWING,OF THEDWV, WATER
 PIPING,PIPE SIZES, MATERIAL.
 WATER HEATER, LOCATION.
 (12) AIR CHAMBERS, COMPLY W/SEC 607.8.3
 USE WATER HAMMER ARRESTORS, AS SPECIFIED
 BY MFG.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096X8233