| Plan Review Notes For Permit 01070541 |
| Permit Number |
01070541 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-13 00:00:00 | 1.PROVIDE AN APPROVED CLASS "A" OR | | | ADDRESSABLE FIRE ALARM SYSTEM THROUGHOUT | | | 2.PROVIDE APPROVED SMOKE DETECTORS IN | | | DORMITORY AREAS. | | | 3. PROVIDE EXIT LIGHTS AT THE EAST AND | | | WEST EXTREMES OF DORMITORY AREAS. | | | 4. PROVIDE EMERGENCY LIGHTING THROUGHOUT | | | TRAINING TOWER. | | | 5. INTERIOR FINISH SHALL BE CLASS A OR B | | | IN EXIT ACCESS AREAS AND CLASS A,B, OR C | | | IN LOBBIES, CORRIDORS AND INDIVIDUAL | | | AND GUEST ROOMS. | | | 6.EACH DORMITORY ROOM SHALL BE PROVIDED | | | WITH A SELF CLOSING, 20 MINUTE FIRE DOOR | | | 7. FIRE RESISTANCE FOR INTERIOR CORRIDOR | | | SHALL BE 30 MINUTES. | | | 8. EVERY HAZARDOUS AREA SHALL BE SEPARAT | | | ED BY 1 HOUR FIRE RESISTANCE RATING. |
|