Plan Review Notes
Plan Review Notes For Permit 01070541
Permit Number 01070541
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-07-13 00:00:001.PROVIDE AN APPROVED CLASS "A" OR
 ADDRESSABLE FIRE ALARM SYSTEM THROUGHOUT
 2.PROVIDE APPROVED SMOKE DETECTORS IN
 DORMITORY AREAS.
 3. PROVIDE EXIT LIGHTS AT THE EAST AND
 WEST EXTREMES OF DORMITORY AREAS.
 4. PROVIDE EMERGENCY LIGHTING THROUGHOUT
 TRAINING TOWER.
 5. INTERIOR FINISH SHALL BE CLASS A OR B
 IN EXIT ACCESS AREAS AND CLASS A,B, OR C
 IN LOBBIES, CORRIDORS AND INDIVIDUAL
 AND GUEST ROOMS.
 6.EACH DORMITORY ROOM SHALL BE PROVIDED
 WITH A SELF CLOSING, 20 MINUTE FIRE DOOR
 7. FIRE RESISTANCE FOR INTERIOR CORRIDOR
 SHALL BE 30 MINUTES.
 8. EVERY HAZARDOUS AREA SHALL BE SEPARAT
 ED BY 1 HOUR FIRE RESISTANCE RATING.