Plan Review Notes For Permit 01070541
Permit Number 01070541
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-07-12 00:00:00FAILED:
 1. PLEASE SUBMIT STORM WATER CALCULATION
 FOR OUR REVIEW AND APPROVAL.
 2. PLEASE INCLUDE DETAILS FOR THE
 PROPOSED DRY RETENTION POUND.
 3. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN FOR ENTIRE SITE.
 4. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY SEWER LATERAL, ON THE
 PROPERTY, AT THE BACK OF THE SIDEWALK.
 5. PLEASE VERIFY IF THERE IS AN EXISTING
 HYDRANT IN FRONT OF PROPOSED DRIVEWAY
 ENTRANCE.
 6. IF GARBAGE IS TO BE PICKED UP BY THE
 CITY, THE DUMPSTER ENCLOSURE SHOULD HAVE
 A MINIMUM OF 12'-6" CLEAR BETWEEN THE
 GATE POSTS AND IT SHOULD BE 12'-6" WIDE
 AND 12' DEEP.
 7. PLEASE COORDINATE WITH PUBLIC
 UTILITIES ENGINEERING SERVICES FOR ALL
 THE NEW CONNECTIONS TO THE CITY SERVICES
 ,659-8040.
 8. A SEPARATE DEP PERMIT WILL BE
 REQUIRED.
 9. A DETAILED REVIEW WILL BE DONE AT THE
 TIME OF ACTUAL PERMITTING, AND WHEN CIVL
 PLANS ARE COMPLETEY DEVELOPED.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI