Plan Review Notes For Permit 01070522
Permit Number 01070522
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2002-04-17 00:00:00A) RELOCATED FIRE HYDRANT MUST BE
 PROVIDED WITH AT LEAST SEVEN FEET SIX
 INCH CLEARANCE TO THE FRONT AND SIDES
 OF IT. ALSO A MINIMUM OF AT LEAST FOUR
 FEET IS TO BE PROVIDED TO THE REAR OF
 IT.
 B) FIRE HYDRANT VALVE IS TO BE NO
 FARTHER THAN FOUR FEET FROM THE FIRE
 HYDRANT.
 C) RELOCATED FIRE HYDRANT IS TO MEET
 CITY UTILITY AND FIRE RESCUE STANDARDS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910