2001-12-20 00:00:00********************DENIED**************
  
 AS PER COUNTYWIDE AMENDMENTS TO THE 1994
 SPC 804.3, AIR CONDITIONING UNITS
 GREATER THAN 3 TON, CONDENSATE SHALL
 TERMINATE INTO AN APPROVED DRYWELL OR
 TO THE STORM DRAINAGE SYSTEM.
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-1989.(2ND REQUEST)
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS AND
 FREEZERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.