Plan Review Notes
Plan Review Notes For Permit 01070522
Permit Number 01070522
Review Stop P
Sequence Number 2
Notes
Date Text
2001-10-10 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) SHT A-1 DEPT OF HOTEL BUSINESS REG-
 ULATION, PLAN REVIEW W/COMMENTS REQUIRED
 BEFORE PLUMBING PLAN REVIEW. FROM PREV-
 IOUS REVIEW, COMMENT RESPONSE ACKNOWLED-
 GED.
 2) SHT C-1, IR-6, P-1, DETAIL(6), GREASE
 TANK, COMMENT FROM PREVIOUS PLAN REVIEW,
 NEED LETTER FROM R. COMPO FOR PLAN RE-
 VIEW. COMMENT RESPONSE ACKNOWLEDGED.
 3) C-4, SITE WORK, TO COMPLY WITH CITY
 OF WPB UTILITY STANDARDS. BACK FLOW PRE-
 VENTERS REQD ON IRRIGATION AND FIRE.
 PLEASE SHOW ON PLANS. COMMENT RESPONSE
 ACKNOWLEDGED. SHOW TYPE AND LOCATION.
 4) GAS PERMIT APPLICATION REQUIREMENTS
 STILL REQUIRED. PLEASE SUBMIT AN ISO-
 METRIC THAT CLEARLY SHOWS "ALL CUT SECT-
 IONS AND CORRESPONDING LENGTHS". PLEASE
 SHOW TYPE OF GAS (NATURAL OR LP).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377