| Plan Review Notes For Permit 01070522 |
| Permit Number |
01070522 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-08 00:00:00 | ******************DENIED**************** | | | | | | | | | 1.DUCT PENETRATING A FIRE RATED WALL | | | IN THE FOOD PREP AREA, INDICATES THE | | | DUCT PENETRATING THE WALL ON AN | | | ANGLE.FIRE DAMPER CANNOT BE | | | INSTALLED IN DUCTWORK AT THIS ANGLE. | | | DUCTWORK SHALL RUN PERPENDICULAR TO | | | THE WALL FOR PROPER INSTALLATION OF | | | THE FIRE DAMPER. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | 3.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 4.CONDENSER UNIT STAND DOES NOT | | | INDICATE HEIGHT REQUIRMENT. 18" | | | MINIMUM FROM ROOF SURFACE TO THE | | | BOTTOM OF THE SUPPORT RAIL. | | | | | | 5.PROVIDE EQUIPMENT SCHEUDLE. | | | | | | 6.ENERGY CALCULATIONS AS PER FLORIDA | | | ENERGY CODE 101.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|