Date Text
2001-10-08 00:00:00******************DENIED****************
  
  
 1.DUCT PENETRATING A FIRE RATED WALL
 IN THE FOOD PREP AREA, INDICATES THE
 DUCT PENETRATING THE WALL ON AN
 ANGLE.FIRE DAMPER CANNOT BE
 INSTALLED IN DUCTWORK AT THIS ANGLE.
 DUCTWORK SHALL RUN PERPENDICULAR TO
 THE WALL FOR PROPER INSTALLATION OF
 THE FIRE DAMPER.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.
  
 3.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 4.CONDENSER UNIT STAND DOES NOT
 INDICATE HEIGHT REQUIRMENT. 18"
 MINIMUM FROM ROOF SURFACE TO THE
 BOTTOM OF THE SUPPORT RAIL.
  
 5.PROVIDE EQUIPMENT SCHEUDLE.
  
 6.ENERGY CALCULATIONS AS PER FLORIDA
 ENERGY CODE 101.1.1.
  