| 2001-09-26 00:00:00 | 1) BUILDING ADDRESS NOTE ON PAGE A-1 | | | IS INCORRECT. CITY CODE 3343-00 | | | REQUIRES ADDRESSES ON BUILDINGS TO BE | | | AT LEAST 6" HIGH, 3" WIDE ON A | | | CONTRASTING BACKGROUND VISIBLE DAY AND | | | NIGHT. | | | 2) AWNINGS IF CANVAS AND PERSONS ARE | | | EXPECTED TO TRAVEL UNDERNEATH THEM ARE | | | TO BE FIRE RETARDANT. | | | 3) EXHAUST FAN LOCATIONS FOR KITCHEN | | | EQUIPMENT ARE TO BE LOCATED A MINIMUM | | | OF AT LEAST 10 FEET FROM ANY AIR | | | INTAKES. | | | 4) PANIC HARDWARE REQUIRED ON ALL EXIT | | | DOORS SINCE SEATING AREA HOLDS 99 | | | PERSONS WITH STAFF WILL BE OVER 100 | | | PERSONS. | | | 5) PROVIDE BOLLARD PROTECTION FOR | | | GAS METER. | | | 6) PLEASE CLEARLY IDENTIFY EMERGENCY | | | LIGHTING EQUIPMENT IN DINING ROOM. | | | ADDITIONAL EXIT SIGNS ARE REQUIRED | | | ABOVE EXIT DOORS THAT ARE NOT | | | PREVENTLY MARKED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|