Plan Review Notes
Plan Review Notes For Permit 01070522
Permit Number 01070522
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-09-26 00:00:001) BUILDING ADDRESS NOTE ON PAGE A-1
 IS INCORRECT. CITY CODE 3343-00
 REQUIRES ADDRESSES ON BUILDINGS TO BE
 AT LEAST 6" HIGH, 3" WIDE ON A
 CONTRASTING BACKGROUND VISIBLE DAY AND
 NIGHT.
 2) AWNINGS IF CANVAS AND PERSONS ARE
 EXPECTED TO TRAVEL UNDERNEATH THEM ARE
 TO BE FIRE RETARDANT.
 3) EXHAUST FAN LOCATIONS FOR KITCHEN
 EQUIPMENT ARE TO BE LOCATED A MINIMUM
 OF AT LEAST 10 FEET FROM ANY AIR
 INTAKES.
 4) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SINCE SEATING AREA HOLDS 99
 PERSONS WITH STAFF WILL BE OVER 100
 PERSONS.
 5) PROVIDE BOLLARD PROTECTION FOR
 GAS METER.
 6) PLEASE CLEARLY IDENTIFY EMERGENCY
 LIGHTING EQUIPMENT IN DINING ROOM.
 ADDITIONAL EXIT SIGNS ARE REQUIRED
 ABOVE EXIT DOORS THAT ARE NOT
 PREVENTLY MARKED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910