| Date |
Text |
| 2001-07-29 00:00:00 | PLUMBING PLAN REVIEW,DENIED |
| | CODE REFERENCES,SPC-94,SGC-97,FACBC-97. |
| | (1)SHT A-1 DEPT.OF HOTEL BUSINESS |
| | REGULATION, PLAN REVIEW W/ COMMENTS |
| | REQUIRED, BEFORE PLUMBING PLAN REVIEW. |
| | CONTACT |
| | 954 -958-5520. |
| | (2)SHT C-1,IR-6, P-1, DETAIL(6), GREASE |
| | TANK, CONTACT W PALM BCH ENVIRONMENTAL |
| | COMPLIANCE, RODNEY COMPO FOR SIZE, |
| | 561- 837- 4074. |
| | (3)C-4,SITE WORK,TO COMPLY WITH CITY OF |
| | WEST PALM BCH. UTILITY STDS, BACK FLOW |
| | PREVENTERS REQ. ON DOMESTIC,IRRIGATION |
| | AND FIRE WATER SUPPLY, ORD# 2853-95. |
| | SHOW TYPE AND LOCATION. |
| | (4)SHT A-11,NO ELV.DETAIL FOR THE URINAL |
| | SEC 4.18.2 HIGHT 17" AFF. |
| | SEC 4.18.3 CLEAR FLR SPACE 30"X 48". |
| | (5)SHT A-11 DETAIL(9),H/C SINK, COMPLY |
| | SEC 4.19.2, HEIGHT & CLEARANCE,NO |
| | HIGHERTHAN 34" AFF. |
| | (6)SHT A-11 DETAIL(9) H/C WATER CLOSET, |
| | SEC 4.17.3,SIZE & ARRANGMENT,FIG 30(E). |
| | DIMENSION OFF THE SIDE WALL 18" |
| | ABSOLUTE(7A) SHT P-1,PLBG PLAN NOTES |
| | #(4) A/C |
| | CONDENSATE DRAINS, COMPLY WITH MCWA-94 |
| | SEC 804. COMMON SYTEM TO STORM, CONNECT |
| | OUTSIDE OF BLDG, WITH A RELIEF VENT. |
| | (7B) ANY REFERENCE TO KITCHEN EQUIPMENT |
| | CONTRACTOR,INSTALLING DRAINS. ALL |
| | PIPINGTO BE INSTALLED BY A LICENSED |
| | PLUMBING |
| | CONTRACTOR. |
| | (8) SHT P-1 NOTES #6 TO #25 COMPLY WITH |
| | MCWA-94 SEC 607.7, NO MORE THAN 2 PLBG. |
| | FIXTURES ON 1/2" C/W,NO MORE THAN 4 |
| | PLBGFIXTURES ON 1/2" H/W. |
| | (9) SHT P-1 NOTE #14 REFERENCE TO OHD, |
| | OTHER REFERENCES TO ID, FUNNEL DRAINS |
| | ORSAFE WASTE (ID). SEC 802. |
| | ALL INDIRECT WASTE TO FLR SINKS. |
| | |
| | (10) SHT P-1 NOTE #19 COMPLY W ITH SEC |
| | 607.8.3,REFERENCE TO AIR CHAMBERS IN |
| | CEILINGS AND WALLS. NOT APPROVED. |
| | USE STD PDI-WH102,INSTALLATION OF WATER |
| | HAMMER ARRESTORS,COMPLY WITH MANFACTURE |
| | INSTRUCTIONS FOR SIZE & PLACEMENT. |
| | (11) SHT P-2 NO DETAIL# GAS ISOMETRIC, |
| | SEE ATTACHED GAS PERMIT APPLICATION RE- |
| | QUIRMENTS. ADDRESS EACH OF (6) ITEMS. |
| | (12) SHT P-2 DETAIL#(9) IRRIATION BACK |
| | FLOW PREVENTER TYPE (RPZV). |
| | (13) SHT P-2 KITCHEN DWV ISOMETRIC AND |
| | SHT P-3 NOTE #7,DISH WASHER TO SANITARY |
| | SEWER,LOCAL ORDINANCE # 2938-96. |
| | END OF COMMENTS, PAUL SCHMITZ |
| | 3QUESTIONS561-659-8096X8233 |