| 2001-08-02 00:00:00 | *******************DENIED*************** |
| | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW: |
| | |
| | 1.FIRE DAMPER INSTALLATION DETAIL, |
| | SHALL COMPLY WITH UL 555 AND BEAR |
| | THE LABLE OF AN APPROVED TESTING |
| | AGENCY. |
| | |
| | 2.FAN SHUTDOWN REQUIRED WITH |
| | NOTIFICATION TO ALARM/STROBE IN |
| | NORMALLY OCCUPIED AREAS, AS PER |
| | 1997 SMC 406.1 AND NFPA 96 4-4.4.3. |
| | PLEASE INDICATE ALARM/STROBE AND |
| | DUCT SMOKE DETECTORS ON PLAN. |
| | |
| | 3.PLEASE INDICATE CONDENSATE DRAIN |
| | LINES ON PLAN AS WELL AS SUPPORT FOR |
| | PIPING.CONDENSATE SHALL COMPLY |
| | WITH 1997 SMC 304.8.3, UNITS LARGER |
| | THAN 3 TONS SHALL DRAIN TO STORM |
| | DRAIN OR AN APPROVED DRYWELL. |
| | |
| | NOTE:ADDITIONAL PERMITS REQUIRED FOR |
| | HOOD, FIRE SUPRESSION, AND WALK |
| | IN COOLERS.PLEASE PROVIDE PLANS |
| | WITH AND MANUFACTURER SUBMITTAL |
| | DATA WITH PERMIT APPLICATION. |
| | |
| | CONDENSER UNIT STANDS SHALL BE |
| | A MINIMUM OF 18" ABOVE THE ROOF |
| | SURFACE TO THE BOTTOM OF THE |
| | SUPPORT RAIL. (AMENDED 1997 SMC |
| | 304.2.5) |
| | |