2001-08-02 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.FIRE DAMPER INSTALLATION DETAIL,
 SHALL COMPLY WITH UL 555 AND BEAR
 THE LABLE OF AN APPROVED TESTING
 AGENCY.
  
 2.FAN SHUTDOWN REQUIRED WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS, AS PER
 1997 SMC 406.1 AND NFPA 96 4-4.4.3.
 PLEASE INDICATE ALARM/STROBE AND
 DUCT SMOKE DETECTORS ON PLAN.
  
 3.PLEASE INDICATE CONDENSATE DRAIN
 LINES ON PLAN AS WELL AS SUPPORT FOR
 PIPING.CONDENSATE SHALL COMPLY
 WITH 1997 SMC 304.8.3, UNITS LARGER
 THAN 3 TONS SHALL DRAIN TO STORM
 DRAIN OR AN APPROVED DRYWELL.
  
 NOTE:ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPRESSION, AND WALK
 IN COOLERS.PLEASE PROVIDE PLANS
 WITH AND MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 CONDENSER UNIT STANDS SHALL BE
 A MINIMUM OF 18" ABOVE THE ROOF
 SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL. (AMENDED 1997 SMC
 304.2.5)
  