Plan Review Notes
Plan Review Notes For Permit 01070522
Permit Number 01070522
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT SHUNT TRIPS
 ARE NOT PERMITTED AS MAIN MEANS OF
 DISCONNECT. MANUAL MEANS MUST BE
 PRIMARYPER 230-76/230-79
  
 2)NOTE: PLEASE NOTE THAT "PP" SHOW 400A
 OCP FOR PANEL"K-1" WITH 3/0 CONDUCTORS
 AS FEED TO "K-1" 310-16
  
  
 PLEASE SUBMIT CLARIFICATION FOR THE
 ABOVE INFORMATION. PLEASE SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372