| Plan Review Notes For Permit 01070522 |
| Permit Number |
01070522 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT SHUNT TRIPS | | | ARE NOT PERMITTED AS MAIN MEANS OF | | | DISCONNECT. MANUAL MEANS MUST BE | | | PRIMARYPER 230-76/230-79 | | | | | | 2)NOTE: PLEASE NOTE THAT "PP" SHOW 400A | | | OCP FOR PANEL"K-1" WITH 3/0 CONDUCTORS | | | AS FEED TO "K-1" 310-16 | | | | | | | | | PLEASE SUBMIT CLARIFICATION FOR THE | | | ABOVE INFORMATION. PLEASE SUBMIT FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|