Plan Review Notes
Plan Review Notes For Permit 01070374
Permit Number 01070374
Review Stop R
Sequence Number 6
Notes
Date Text
2001-12-26 00:00:005TH CHECKLIST:
 1-PRODUCT APPROVAL INFORMATION SUBMITTED
 STILL IS NOT ACCEPTABLE.
 A)SITE SPECIFIC FORM NEEDS TO BE SIGNED,
 SEALED & DATED BY ARCHITECT OF RECORD
 AS WELL.
 B)DESIGN PRESSURES SPECIFIED FOR THE
 SLIDING GLASS DOORS ARE INCORRECT.
 THOSE ARE THE RESULT PRESSURES, NOT
 THE DESIGN PRESSURES. THEREFORE, THIS
 PRODUCT APPROVAL IS NOT ACCEPTABLE.
 SEE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT OF RECORD.
 C)PRODUCT APPROVAL IS FOR CASEMENT
 WINDOWS.THERE ARE NOT CASEMENT WINDOWS
 IN THIS PROJECT. SEE ARCHITECT'S PLANS
 D)ENGINEER TO SEE ARCHITECT'S PLANS TO
 SEE SIZES AND TYPE OF GLASS REQUIRED
 ACCORDING TO LOCATION. (SAFETY GLASS
 REQUIRED AT HAZARDOUS LOCATIONS.
 SECTION2405.2 SBC 1997).
 E)PROVIDE COMPLETE PRODUCT APPROVAL
 INFORMATION FOR WINDOW MULLIONS.
  
 2-OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS AS REQUIRED BY
 SEC. 103.1 FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION, 1997.