| Plan Review Notes For Permit 01070374 |
| Permit Number |
01070374 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-02 00:00:00 | CHECKLIST: | | | 1-NEED ENERGY CALCULATIONS ON FORM | | | 600A-97 AS REQUIRED BY SECTION 101.2.2 | | | OF FLORIDA ENERGY EFFICIENCY CODE FOR | | | BUILDING CONSTRUCTION, 1997 EDITION. | | | -INFORMATION SUBMITTED ARE NOT THE | | | ENERGY CALCULATIONS. | | | 2-PROVIDE PRODUCT APPROVAL FOR: | | | A)SLIDING GLASS DOORS WITH SIZE AND | | | DESIGN PRESSURES AS SPECIFIED ON | | | ARCHITECT'S PLANS. | | | -PRODUCT APPROVAL SUBMITTED DOESN'T | | | MEET EITHER ONE. | | | C)FIXED WINDOWS WITH THE SIZE SHOWN IN | | | ARCHITECT'S PLANS. | | | -PRODUCT APPROVAL SUBMITTED IS FOR | | | WINDOWS UP TO 120" IN WIDTH AND UP TO | | | 60" IN HEIGHT. SEE ARCHITECT'S PLAN | | | FOR SIZE SPECIFIED. | | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS. | | | -CLEARLY INDICATE ON SHUTTER DRAWINGS | | | THE SPECIFIC MOUNTING CONDITIONS AND | | | ALL THE SPECIFIC COMPONENTS TO BE USED | | | ON THIS PROJECT. | | | -IF INFORMATION IS NOT COMPLETE AT THIS | | | TIME, THEN SUB-CONTRACTOR MAY APPLY | | | FOR A SEPARATE PERMIT IN ORDER TO | | | EXPEDITE THE BUILDING PERMIT. |
|