Plan Review Notes
Plan Review Notes For Permit 01070374
Permit Number 01070374
Review Stop R
Sequence Number 2
Notes
Date Text
2001-09-24 00:00:00CHECKLIST:
 1-NEED ENERGY CALCULATIONS AS REQUIRED
 BY SECTION 101.2.2 OF STATE OF FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 2-CLARIFY HOW IS TRUSS ANCHOR TAPR
 ANCHORED TO EXISTING TIE BEAM.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED BY
 SEC. 2405.2 SBC 1997. SEE PLANS.
 4-PROVIDE PRODUCT APPROVAL FOR:
 A)FLAT ROOF SYSTEM TO BE USED.
 B)SLIDING GLASS DOORS WITH THE SIZES AND
 AND THE DESIGN PRESSURES AS SHOWN ON
 THE ARCHITECT'S PLANS.
 C)FIXED WINDOWS WITH THE SIZE AS SHOWN
 ON ARCHITECT'S PLANS.
  
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS:KEY PLAN, INSTALLATION SCHEDULE
 AND CLEARLY INDICATE ON DRAWINGS THE
 SPECIFIC MOUNTING CONDITIONS TO BE
 USED.
 -IF COMPLETE INFORMATION IS NOT
 PROVIDE A TIME OF RESUBMITTAL, THEN A
 SEPARATE PERMIT MAY BE APPLIED FOR.
 6-OWES ADDITIONAL FEES OF $315.28 FOR
 UPDATED BUILDING VALUATION AND RADON
 FEES. PLEASE PAY ATTACHED RECEIPT.
 7-SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AS REQ'D BY SEC. 2305 SBC/97.
 SEE SHEET #6 FOR COMMENTS.