2001-09-17 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS NOW
 INCLUDE A RISER DIAGRAM WITH NEW EQUIP-
 -MENT BEING INSTALLED.
 PLEASE NOTE, NEED TO SUBMIT AIC RATINGS
 FOR ALL NEW EQUIPMENT/MAIN/PANELS.
 PER 110-9/215-5
  
 2)NOTE: PLEASE CLARIFY 10 GFI CIRCUITS
 SHOWN ON PANEL SCHEDULE. PLEASE NOTE
 THAT TWO SMALL APPLIANCE CIRCUITS ARE
 REQ`D BY 210-52-B1
  
 3)NOTE: PLEASE LABEL GFI CIRCUIT FOR
 BATH.210-11-C-3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  