| Notes |
| Date |
Text |
| 2001-09-17 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NOW | | | INCLUDE A RISER DIAGRAM WITH NEW EQUIP- | | | -MENT BEING INSTALLED. | | | PLEASE NOTE, NEED TO SUBMIT AIC RATINGS | | | FOR ALL NEW EQUIPMENT/MAIN/PANELS. | | | PER 110-9/215-5 | | | | | | 2)NOTE: PLEASE CLARIFY 10 GFI CIRCUITS | | | SHOWN ON PANEL SCHEDULE. PLEASE NOTE | | | THAT TWO SMALL APPLIANCE CIRCUITS ARE | | | REQ`D BY 210-52-B1 | | | | | | 3)NOTE: PLEASE LABEL GFI CIRCUIT FOR | | | BATH.210-11-C-3. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|