2001-07-31 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-NEED TO FILE NOTICE OF COMMENCEMENT.
 3-PROVIDE ENERGY CALCULATIONS.
 4-PROVIDE SOIL TEST REPORT.
 5-SPECIFY VENTILATION FOR ROOF AS REQ'D
 BY SEC. 2309.7.2 SBC 1997.
 6-TRUSS ANCHOR SCHEDULE:
 -CONNECTOR SEMCO RTPGA IS A WOOD TO
 WOOD CONNECTOR. NOT WOOD TO CONCRETE.
 REVISE AS REQUIRED.
 -CLARIFY HOW IS CONNECTOR TAPR EMBEDED
 INTO EXISTING TIE BEAM.
 7-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. SEE
 COMMENTS ON FORM.
 8-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEC 2405.2 SBC/97. SEE FLOOR PLAN.
 9-NEED PRODUCT APPROVAL FOR: (2 COPIES)
 -FLAT ROOF SYSTEM.
 -CLAY BARREL TILE.
 -SLIDING GLASS DOORS.
 -SINGLE HUNG WINDOWS.
 -FIXED WINDOWS.
 10-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS. INSTALLATION SCHEDULE
 KEY PLAN, ETC.