| Plan Review Notes For Permit 01070374 |
| Permit Number |
01070374 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-07 00:00:00 | *******************DENIED*************** | | | INSUFFICIENT INFORMATION | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | | | | 1.MAKE, MODEL, SEER, BTU, AND KW HEAT | | | STRIP FOR AHU/CONDENSER. | | | | | | 2.PROVIDE MATERIAL AND R-VALUE FOR | | | DUCT BEING INSTALLED. | | | | | | 3.SIZE OF GRILLS AND CFM BEING | | | DISTRIBUTED. | | | | | | 4.PLEASE PROVIDE ENERGY CALCULATIONS | | | TO SHOW COMPLIANCE WITH FLORIDA | | | ENERGY EFFICIENCY CODE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|