| Plan Review Notes For Permit 01070374 |
| Permit Number |
01070374 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | AND SHOW EXISTING SERVICE SIZE. | | | 220-3-C-1 | | | | | | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | INCLUDING ISLAND. | | | | | | 3)NOTE" PLEASE PROVIDE PANEL SCHEDULE OF | | | MIN REQ`D CIRCUITS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|