| Plan Review Notes For Permit 01070299 |
| Permit Number |
01070299 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-01-08 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | PREVIOUS COMMENTS FROM 7-27-01 | | | 4) SHT P-2 CONDENSATE DRAIN TIED INTO | | | STORM DRAIN SHALL HAVE A RELIEF VENT IN | | | CASE OF BACK-UP OF STORM WATER. | | | 8) SHT A1.3, TURNING RADIUS TO BE IN | | | TOILET ROOM NOT STALL. CLEAR FLOOR SPACE | | | TO BE SHOWN FOR HDCP URNAL AND DOOR FROM | | | STALL SHALL NOT SWING INTO THAT CLEAR | | | FLOOR SPACE. | | | PREVIOUS COMMENTS FROM 11-18-01 | | | 1) SHT A1.4 TEACHERS PLANNING ROOM, SHOW | | | CLEAR FLOOR SPACE FOR SINK AND KNEE | | | CLEARANCE PER FACBC SEC 4.24 | | | 2) SHT A1.3, RM #102 PROVIDE CODE REFER- | | | ENCE, CHILDERNS H/C PLUMBING FIXTURES | | | FOR DIMENSIONS, GRAB BARS, DOOR SWING. | | | NOT FOUND, PLEASE CALL OUT RESPONSE. | | | 4) SHT P-2 RM'S 401 & 501, BACKFLOW DE- | | | VISES SHALL BE NO HIGHER THAN 4' ABOVE | | | FINISH FLOOR FOR SERVICE. | | | 5) SHT P-3 WASTE & VENT RISER, TAB 714.1 | | | FIXTURE LOAD NOT ADDRESSED, REQUIRED TO | | | SIZE BLDG DRAIN. | | | 5B) SHT P-3 TWO WAY C/O AT BLDG DRAIN & | | | BLDG SEWER NOT ADDRESSED. SPC SEC 710(6) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|