| 2002-01-07 00:00:00 | BUILDING PLAN REVIEW |
| | ******PROVISO******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE |
| | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) |
| | |
| | --PROVISO-- |
| | SBC* 104.1.1SEPARATE PERMIT |
| | APPLICATION IS REQUIRED FOR THE |
| | ALUMINUM SHUTTERS. |
| 2002-01-04 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE |
| | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) |
| | |
| | THE FOLLOWING REVIEW COMMENTS ARE |
| | NUMBERED AS PER THE RELEVANT ITEM FROM |
| | THE BUILDING PLAN REVIEW OF 12/03/01: |
| | |
| | 9) PRODUCT APPROVALS.NONE OF THE |
| | APPROVALS SUBMITTED ARE APPLICABLE TO |
| | DOOR 105-1 (TYPE D), DOOR 002-2 (TYPE B) |
| | OR WINDOW TYPES C, D AND E.ALSO, THE |
| | DIMENSIONS AND CONFIGURATION OF WINDOW |
| | TYPES A, B, F AND G ARE OUTSIDE THE |
| | SCOPE OF THE SUBMITTED PRODUCT APPROVAL. |
| | SUBMIT PRODUCT APPROVALS TO COVER THE |
| | TYPES OF WINDOWS AND DOORS PROPOSED. |
| | |
| | 13) PROVISO: SHEET A5.3 SHALL BE REVISED |
| | TO SUIT THE AMENDED STAIRCASE |
| | ARRANGEMENT ON SHEETS A1.1 AND A1.2. |
| | |
| | 14) PROVISO: A SEPARATE APPLICATION IS |
| | REQUIRED FOR THE AWNINGS. |