| 2001-11-18 00:00:00 | PLUMBING PLAN REVIEW,DENIED |
| | CODE REFERENCES STANDARD PLUMBING-94 |
| | FLORIDA ACCESSIBILITY CODE-97 |
| | PREVIOUS COMMENTS NOT ADDRESSED 07-27-01 |
| | (4) SHT P-2 CONDENSATE DRAIN TERMINATION |
| | NOT SHOWN ON SHT C-1, CIVIL PLANS. |
| | (8) SHT A1.3, 1ST, 2ND FLR BOYS & GIRLS |
| | TOILET RM'S, COMPLY W/SEC 4.2.3 & 4.22.3 |
| | TOILET RM WHEEL CHAIR TURNING SPACE, SEE |
| | FIG 30(E) FOR STALLS, URINALS MAX HIGTH |
| | SEC 4.18.2, CLEAR FLR SPACE SEC 4.18.3 |
| | NEW COMMENTS DATED 11-18-01PES |
| | (1) SHT A1.4 TEACHERS PLANNING RM OR |
| | ( BREAK RM.) SEC 4.24 SINK HGTH, 34"FF |
| | CLEAR FLR SPACE 30"X 48", KNEE CLEARANCE |
| | (2) SHT A1.3, RM #102 PROVIDE CODE REFER |
| | ENCE, CHILDERNS H/C PLUMBING FIXTURES. |
| | FOR DIMENSIONS, GRAB BARS, DOOR SWING. |
| | (3) SHT A2.1,2 PARAPET DETAIL, PROVIDE |
| | CALCULATIONS FOR SCUPPER DRAINS, SIZE |
| | LOCATION, 1/2 THE VERTICAL WALLS 1108.3 |
| | SEE TAB 1109.3, RATE OF RAINFALL 8.5" |
| | (4) SHT P-2 RM 401,501 JANITORS CLOSET |
| | SPRINKLER HEAD, COMPLY WITH SEC 606.3 & |
| | 606.1 ADEQUATE PROTECTION OF POTABLE |
| | WATER SHALL BE PROVIDED FROM UNSAFE |
| | SYSTEM TO A SAFE SYSTEM, PROVIDE INFOR- |
| | MATION ON TYPE OF BACKFLOW PROTECTION. |
| | (5A)SHT P-3 WASTE & VENT RISER,TAB 714.1 |
| | PROVIDE FIX UNIT LOAD TO SIZE BLDG DRAIN |
| | (5B) TWO WAY CO. REQUIRED AT JUNCTION OF |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | SEC 710(6). |
| | (6) SHT P-3,4 DETAILS OF WATER PIPING, |
| | COMPLY W.SEC 607.8.1,WATER HAMMER ARREST |
| | ORS SHALL BE SIZED AND INSTALLED AS PER |
| | PDI-WH201, NOT AT THE HIGH POINT OF THE |
| | SYSTEM.SPECIFY TYPE AND MANFACTURE. |
| | END OF COMMENTSPAUL SCHMITZ |