| 2001-11-29 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE CLARIFY FCU-1 & FCU-2 IN THE | | | STAIRWELL.THERE SHALL BE NO | | | MECHANICAL EQUIPMENT IN STAIRWELL AS | | | PER THE 2000, 101LIFE SAFETY CODE. | | | | | | PLAN SHEET M-4 - DUCT PENETRATIONS FOR | | | ONE HOUR WALL NOTE 1, DUCTS ARE 100 | | | SQUARE INCHES IN AREA OR SMALLER. | | | PLEASE CLARIFY WHAT PENETRATIONS ARE | | | LESS THAN 100 SQ INCHES.PLEASE NOTE, | | | NOT ALL DUCTS ARE IDENTIFIED WITH A | | | DUCT SIZE. | | | | | | PLEASE NOTE EXHAUST OUTLETS FOR DUCTS | | | CONVEYING NOXIOUS GASES FLAMMABLE | | | VAPORS, AND CORROSIVE VAPORS SHALL | | | TERMIATE OUTSIDE THE BUILDING AND SHALL | | | BE LOCATED 10' FROM ANY ADJACENT | | | BUILDING, PARKING AREA, ADJACENT | | | PROPERTY LINE, WINDOW, DOOR, OR AIR | | | INTAKE OPENING AND SHALL BE LOCATED AT | | | LEAST 10' ABOVE THE ADJOINING GRADE | | | LEVEL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|