| Date |
Text |
| 2001-12-06 00:00:00 | SUMMARY OF CONSULTATION MEETING HELD ON |
| | 12/6/01 REGARDING COMMENT NO 17 OF |
| | 12/3/01 PLAN REVIEW (SEE BELOW): |
| | |
| | 17) SBC 1004.3.1, SBC 1004.3.2 AND |
| | SBC 1004.3.5 ACCESSIBLE MEANS OF EGRESS, |
| | AREAS OF REFUGE: |
| | WHERE MORE THAN ONE REGULAR MEANS OF |
| | EGRESS IS REQUIRED, NOT LESS THAN TWO |
| | ACCESSIBLE MEANS OF EGRESS SHALL BE |
| | PROVIDED.EACH STAIR WHICH IS TO BE |
| | CONSIDERED PART OF AN ACCESSIBLE MEANS |
| | OF EGRESS SHALL EITHER INCORPORATE AN |
| | AREA OF REFUGE OR BE ACCESSED FROM AN |
| | AREA OF REFUGE. |
| 2001-12-03 00:00:00 | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE |
| | SBC* = STANDARD BUILDING CODE (AMENDMENT |
| | S) |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | FL ENERGY CODE = FLORIDA ENERGY EFFICIEN |
| | CY CODE FOR BUILDING CONSTRUCTION |
| | |
| | |
| | THE FOLLOWING REVIEW COMMENTS ARE |
| | NUMBERED AS PER THE RELEVANT ITEM FROM |
| | THE 8/10/01 BUILDING PLAN REVIEW AND THE |
| | LETTER OF RESPONSE DATED 10/24/01: |
| | |
| | 3) SBC* 1804.2.7.2(3)NO SOILS REPORT |
| | WAS ATTACHED TO THE LETTER OF RESPONSE. |
| | |
| | 7) SHEET S-4. DESIGN PARAMETERS. |
| | REFERENCE TO SBC 1999 SHALL BE CORRECTED |
| | TO READ SBC 1997. |
| | |
| | 8) FL ENERGY CODE 103.0ENERGY CODE |
| | COMPLIANCE FORMS SHALL BE SUBMITTED AND |
| | A CERTIFICATE OF COMPLIANCE SHALL BE |
| | SUBMITTED. |
| | |
| | 9) PRODUCT APPROVALS.AS PREVIOUSLY |
| | STATED, THE PERMIT CANNOT BE ISSUED |
| | UNTIL THE REQUIRED PRODUCT APPROVAL TEST |
| | REPORTS ARE SUBMITTED. ALTERNATIVELY, |
| | THE REPORTS CAN BE SUBJECT TO A SEPERATE |
| | PERMIT APPLICATION WITH ASSOCIATED FEES. |
| | |
| | 13) SBC 1007.5.5HANDRAILS SHALL |
| | CONTINUE TO SLOPE BEYOND THE BOTTOM |
| | RISER BY A DISTANCE EQUAL TO THE DEPTH |
| | OF ONE TREAD.ON SHEET A5-3, THE 1ST |
| | FLOOR PLANS 01 AND 02 DO NOT SHOW |
| | HANDRAILS EXTENDING THE REQUIRED |
| | DISTANCE BEYOND THE BOTTOM RISER.NOTE |
| | THAT THE REQUIREMENTS OF SBC 1007.4.2 IN |
| | RESPECT OF LANDING WIDTH MUST BE |
| | OBSERVED. |
| | |
| | 14) SBC* 104.1.1A SEPARATE PERMIT |
| | APPLICATION IS REQUIRED FOR AWNINGS (SEE |
| | WINDOWS AND DOORS UNDER SBC* 104.1.1) |
| | |
| | 16) FL ACC CODE 4.3SUBMIT FURTHER |
| | INFORMATION REGARDING THE WALKWAY LEVELS |
| | ON THE EXISTING COVERED WALK AND NEW |
| | WALKWAY/RAMP LEADING TO THE RETAINED |
| | ONE-STOREY CBS BUILDING.SUBMIT |
| | INFORMATION REGARDING THE SLOPE AND |
| | WALKWAY LEVELS LEADING TO THE WEST |
| | STAIRCASE EXIT DOOR.THE HEIGHT OF THE |
| | GUARDING TO THE PROPOSED CONCRETE RAMP |
| | SHALL BE INCREASED TO 36" (SBC 1015.2) |
| | |
| | 17) SBC 1004.3.1, SBC 1004.3.2.1, |
| | SBC 1004.3.5 ACCESSIBLE MEANS OF EGRESS, |
| | AREAS OF REFUGE: |
| | |
| | PENDING CONSULTATION WITH |
| | CAPTAIN MIKE CARSILLO ON |
| | WEDNESDAY 12/5/01 |
| | |
| | 18) FL ACC CODE 4.5.1ADD NOTES TO THE |
| | PLANS STATING THAT ALL FLOORING SURFACES |
| | ARE TO COMPLY WITH THE ABOVE.NOTE THAT |
| | APPENDIX A (COMMENTARY OF THE AMERICANS |
| | WITH DISABILITIES ACT ACCESSIBILITY |
| | GUIDELINES (ADAAG)) A4.5.1 RECOMMENDS A |
| | MINIMUM STATIC COEFFICIENT OF FRICTION |
| | OF 0.6 FOR ACCESSIBLE ROUTES AND 0.8 FOR |
| | RAMPS. |