| Plan Review Notes For Permit 01070299 |
| Permit Number |
01070299 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-06 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89.PROVIDE AIR | | | BALANCE SCHEDULE TO SHOW COMPLIANCE | | | WITH 1997 SMC 501.2. | | | | | | PLEASE PROVIDE INFORMATION ON "KILN" | | | HOW IS IT BEING VENTED. WHAT IS THE | | | KILN USED FOR?PLAN A1.4 INDICATES ROOM | | | 201A IS A STORAGE ROOM WHERE THE KILN | | | IS LOCATED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. | | | | | | CALLED MARION CONSTRUCTION CO., LETTER F | | | ROM ENGINEER NEEDS TO REFERENCE PLAN REV | | | ISION FOR 7-24-01.ALSO NEED TO COPIES | | | OF LETTER SIGNED, SEALED AND DATED. | | | | | | PLANS OKAY. |
|