| Plan Review Notes For Permit 01070273 |
| Permit Number |
01070273 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-07-09 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) FROM PREVIOUS REVIEW: PLEASE SHOW ALL | | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | | LOCATION AND SQ FT FOR ALL DRAINS, SIZE | | | OF DOWNSPOUTS. SHOW TOTAL SIZE OF ROOF | | | BEING DRAINED, ADD 1/2 AREA OF ALL VERT- | | | ICAL WALLS. PLEASE SUBMIT CALCULATIONS. | | | - RESPONSE NOTED, BUT INFORMATION NOT | | | SUFFICIENT. DOWNSPOUTS AND SECONDARY | | | DRAINS NOT FOUND ON ARCHITECTURAL PLANS | | | AS STATED IN RESPONSE. | | | 2) SHTS P6.1/P6.2 WATER RISER DIAGRAM. | | | FROM PREVIOUS REVIEW: WATER HAMMER ARRES | | | TORS SHALL BE LOCATED AT QUICK CLOSING | | | VALVES. (IN KITCHEN - FOR DISHWASHER & | | | ICE MAKER). RESPONSE NOTED, MORE W.H.A'S | | | REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|