Plan Review Notes
Plan Review Notes For Permit 01070273
Permit Number 01070273
Review Stop P
Sequence Number 4
Notes
Date Text
2002-07-09 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) FROM PREVIOUS REVIEW: PLEASE SHOW ALL
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 LOCATION AND SQ FT FOR ALL DRAINS, SIZE
 OF DOWNSPOUTS. SHOW TOTAL SIZE OF ROOF
 BEING DRAINED, ADD 1/2 AREA OF ALL VERT-
 ICAL WALLS. PLEASE SUBMIT CALCULATIONS.
 - RESPONSE NOTED, BUT INFORMATION NOT
 SUFFICIENT. DOWNSPOUTS AND SECONDARY
 DRAINS NOT FOUND ON ARCHITECTURAL PLANS
 AS STATED IN RESPONSE.
 2) SHTS P6.1/P6.2 WATER RISER DIAGRAM.
 FROM PREVIOUS REVIEW: WATER HAMMER ARRES
 TORS SHALL BE LOCATED AT QUICK CLOSING
 VALVES. (IN KITCHEN - FOR DISHWASHER &
 ICE MAKER). RESPONSE NOTED, MORE W.H.A'S
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377