Plan Review Notes
Plan Review Notes For Permit 01070273
Permit Number 01070273
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2002-09-03 00:00:001) EXISTING FIRE EXIT STAIR IS NOT
 TO BE REMOVED. IT CAN BE REPLACED
 WITH ANOTHER ONE SO LONG AS IT
 COMPLIES WITH ALL APPROPRIATE
 BUILDING AND FIRE CODE REQUIREMENTS.
 THIS EXISTING DEVICE CANNOT BE REMOVED
 AS A DEAD-END CORRIDOR WOULD EXIST
 THAT EXCEEDS CODE REQUIREMENTS.
  
 2) ENSURE ALL DEVICES ARE PLACED
 ON THE BUILDING'S PROPERTY NOT
 SOMEONE ELSE'S.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910