Plan Review Notes
Plan Review Notes For Permit 01070273
Permit Number 01070273
Review Stop P
Sequence Number 3
Notes
Date Text
2002-04-18 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT PO.1 NOTE #13 AIR CHAMBERS IF IN-
 STALLED SHALL BE ACCESSIBLE AND RECHARG-
 ABLE. (SEE ATTACHED SHEET FOR APPROVED
 AIR CHAMBERS). APPROVED WATER HAMMER
 ARRESTORS DO NOT REQUIRE ACCESS AND DO
 NOT REQUIRE TO BE RECHARGED. SUGGEST
 USING APPROVED WATER HAMMER ARRESTORS.
 2) SHT P0.1 SUBMIT MANUFACTURE INFORMAT-
 ION FOR TANKLESS WATER HEATERS.
 3) SHT P3.2 LAUNDRY ROOM HEATER, 1" PAN
 DRAIN REQUIRED NOT 3/4" AS SHOWN.
 4) SHT P3.2 - SHT P5.2 LAUNDRY ROOM
 FLOOR DRAIN REQUIRED WITH TRAP PRIMER.
 SPC SEC 409.4.5
 5) SHT P4.1 PLEASE SHOW ALL PRIMARY &
 SECONDARY ROOF DRAINS. SHOW LOCATION,
 SQUARE FOOTAGE AREA FOR EACH DRAIN, SIZE
 OF DRAINS, AND SIZE OF STORM DRAINAGE
 PIPING. SHOW TOTAL SQUARE FOOTAGE OF
 ROOF BEING DRAINED. ADD 1/2 AREA OF ALL
 VERTICAL WALLS AND AREA OF ROOFS DRAIN-
 ING FROM ABOVE. PLEASE SUBMIT ALL CAL-
 CULATIONS
 6) SHTS P6.1/P6.2 DOMESTIC WATER ISO-
 METRIC EAST/WEST. WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE"
 CLOSE TO FIXTURES, NOT AT TOP OF DROPS
 AS SHOWN. PDI-WH 201 & MANUFACTURE IN-
 STALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377