| Plan Review Notes For Permit 01070273 |
| Permit Number |
01070273 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-04-26 00:00:00 | MECHANICAL PERMIT 01020462 | | | | | | | | | AS PER THE COUNTYWIDE AMMENDMENTS TO THE | | | 1997 SMC 610.1.3 #2, WHERE BRANCH DUCTS | | | CONNECT TO RETURN RISERS IN WHICH THE | | | AIR IS UPWARD IN THE SUBDUCT, RISER | | | SHALL BE CARRIED UP AT LEAST 22" INSIDE | | | THE SUBDUCT.SUBDUCT MUST BE A MINIMUM | | | OF 26 GA. GALVANIZED OR EQUIVALENT. | | | RISERS WHICH ARE SUBJECT TO MOISTURE | | | SHALL BE LINED WITH SUITABLE MATERIAL | | | TO PREVENT DETERIORATION OF DRYWALL | | | ENCLOSURE.EACH UNIT SHALL HAVE A | | | BACKDRAFT DAMPER AS TO PREVENT | | | INFLITRATION CAUSED BY PRESSURE | | | DIFFERNTIAL. | | | | | | PLAN SHEET A9.01 DETAIL #3, 1 HOUR | | | RATED SHAFT UL 415.UL415 IS FOR A NON | | | BEARING WALL NOT A 1 HR SHAFT.PLEASE | | | CORRECT. | | | | | | CHECK WITH NANCY - | | | PLAN SHEET M-2 O.A. FROM THE FIRST FL TO | | | THE AHU FD AT PENETRATION AHU 5 SUPPLY | | | TO CORRIDOR FD IN SUP & RET. | | | | | | PLAN SH M-3 AHU 4 SUP & RET TO CORRIDOR | | | & STAIRWELL BOTH HAVE FIRE DAMPERS.COR | | | RIDOR RADIANT DAMPERS IN CEILING. |
|