Plan Review Notes
Plan Review Notes For Permit 01070273
Permit Number 01070273
Review Stop M
Sequence Number 3
Notes
Date Text
2002-04-26 00:00:00MECHANICAL PERMIT 01020462
  
  
 AS PER THE COUNTYWIDE AMMENDMENTS TO THE
 1997 SMC 610.1.3 #2, WHERE BRANCH DUCTS
 CONNECT TO RETURN RISERS IN WHICH THE
 AIR IS UPWARD IN THE SUBDUCT, RISER
 SHALL BE CARRIED UP AT LEAST 22" INSIDE
 THE SUBDUCT.SUBDUCT MUST BE A MINIMUM
 OF 26 GA. GALVANIZED OR EQUIVALENT.
 RISERS WHICH ARE SUBJECT TO MOISTURE
 SHALL BE LINED WITH SUITABLE MATERIAL
 TO PREVENT DETERIORATION OF DRYWALL
 ENCLOSURE.EACH UNIT SHALL HAVE A
 BACKDRAFT DAMPER AS TO PREVENT
 INFLITRATION CAUSED BY PRESSURE
 DIFFERNTIAL.
  
 PLAN SHEET A9.01 DETAIL #3, 1 HOUR
 RATED SHAFT UL 415.UL415 IS FOR A NON
 BEARING WALL NOT A 1 HR SHAFT.PLEASE
 CORRECT.
  
 CHECK WITH NANCY -
 PLAN SHEET M-2 O.A. FROM THE FIRST FL TO
 THE AHU FD AT PENETRATION AHU 5 SUPPLY
 TO CORRIDOR FD IN SUP & RET.
  
 PLAN SH M-3 AHU 4 SUP & RET TO CORRIDOR
 & STAIRWELL BOTH HAVE FIRE DAMPERS.COR
 RIDOR RADIANT DAMPERS IN CEILING.