2002-07-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES IN
 THE PLANS,AND RESUBMIT FOR REVIEW;
  
 1} THE UNITS LABELED "F,D"AND"C,F" ON
 THE ARCHITECTURAL SHEETS A2.02 AND
 A3.03 STILL ARE INCONSISTENT AND DO NOT
 CORRELATE WITH THE SHEETS IN THE
 ELECTRICAL PLAN THAT CONSISTENTLY LIST
 THEM AS TYPES "D" AND "F".PLEASE CLARIFY
  
 2} THE HALL LIGHTING ON SHEET E2.1 NEEDS
 A 4-WAY SWITCH.
  
 3} SHEET M-1 LISTS THE AHU AS #6,SHEET
 SHEET E3.1 LISTS IT AS AHU #4,WHICH
 AGREES WITH PANEL SCHEDULE"LHP"AND
 THE EQUIPMENT SCHEDULE ON SHEET
 M-8.PLEASE CORRECT.
  
 4} AHU'S #5 AND #6 DO NOT APPEAR ON THE
 ELECTRICAL PLANS,EXCEPT ON PANEL
 SCHEDULE "LHP",PLEASE INDICATE THEIR
 LOCATIONS AND SHOW DISCONNECTS.
  
 5} SHEET M-2 SHOWS THE WASHERS,DRYERS
 AND WATER HEATER IN A DIFFERENT
 LOCATION THAN SHEETS E3.2 AND
 A2.02,PLEASE CORRELATE THESE DRAWINGS
 TO SHOW THE CORRECT LOCATIONS.
  
 6} WATER HEATER DISCONNECT LOCATION
 SHOWN ON SHEET E3.2 WOULD NOT COMPLY
 WITH 110-26.(NOTE:THE HEATER IS IN
 SIGHT OF PANEL "L2".)
  
 7} PLEASE NOTE THAT THE DISCONNECTS FOR
 THE WATER HEATERS LOCATED IN THE CLOSETS
 OF THE UNITS MUST COMPLY WITH 110-26.
  
 8} PLEASE NOTE THAT THE CIRCUIT NUMBERS
 ON SHEET E3.4 MUST CORRELATE WITH THE
 PANEL SCHEDULES FOR THE CONDENSERS.
  
 9} PLEASE INDICATE THE TYPE AND SIZE OF
 THE CONDUIT AND CONDUCTORS FEEDING "L2"
 ON SHEET E5.6.
  
 10} PLEASE INDICATE FEEDER CONDUCTOR AND
 CONDUIT TYPE AND SIZE FOR THE "FUTURE"
 METERS AND DISCONNECTS IF THEY ARE BEING
 INSTALLED UNDER THIS PERMIT.
  
 11} PANEL"LHP" ON SHEET E5.1 IS SHOWN
 BEING FED WITH A 3"PVC CONDUIT,IF IT IS
 SHOWN AS THAT ON THE STAMPED PLANS IT
 MUST BE INSTALLED.
  
 12} THE LOCATION OF THE CATV BOARD SHOWN
 ON RISER SHEET E5.1,IS NOT SHOWN ON THE
 PLAN. PLEASE VERIFY THE SIZE AND NUMBER
 OF THE FEEDERS FOR THIS SYSTEM.ONE 4"
 IS SHOWN,SAME AS THE TELEPHONE RISER.
  
 13} PLEASE VERIFY THE DIMENSIONS OF THE
 ELECTRIC ROOM ON SHEET A2.01 AND E2.1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  