| 2002-04-30 00:00:00 | THE PLANS DECLARE AN NFPA 13R DESIGN |
| | FIRE SPRINKLER SYSTEM.SEE FOOTNOTE |
| | {D} TO SBC TABLE 500.THERE FORE THE |
| | BUILDING IS REQUIRED TO BE ONE HOUR |
| | PROTECTED ORA COMPLETE 13 SYSTEM FOR |
| | THE THREE STORY REQUIREMENT. |
| | |
| | FURTHER, EGRESS WINDOWS, FIRE RATED |
| | CORRIDORS, AND ANY OTHER REDUCTIONS |
| | TAKEN FOR FIRE SPRINKLER SYSTEM ARE NOT |
| | APPLICABLE TO THIS BUILDING.SEE ALSO |
| | SBC 903.2. |
| | |
| | WHERE THE ROOF IS USED FOR EXIT ACCESS |
| | IT MUST COMPLY WITH SBC 1006.2 FOR |
| | SEPARATION FROM THE INTERIOR OF THE |
| | BUILDING. |
| | |
| | SHOW THE DETAILS FOR THE THIRD FLOOR |
| | EXTERIOR STAIR WITH REGARDS TO |
| | DIMENSIONS, DESIGN LOADS, HAND AND |
| | GUARD RAILS.SEE SBC 1007. |
| | |
| | THE PLANS DO NOT CLEARLY INDICATE THE |
| | FIRE RATED TENANT SEPARATION REQUIRED |
| | BY SBC 704.3.INCLUDING AT THE |
| | "CORRIDOR SIDE". |
| | |
| | DOES THE EXIT DISCHARGE ON THE WEST |
| | SIDECOMPLY WITH SBC 1010? |
| | |
| | SHEET A9.01.SHOW A SPECIFIC FRAMING |
| | DETAIL FOR THE SOFFIT CONSTRUCTION. |
| | HOW IS THE FIRE RATED SEPARATION |
| | BETWEEN FLOORS MAINTAINED?HOW IS THE |
| | MECHANICAL EQUIPMENT SUPPORTED AND |
| | ACCESSED?SEE SBC 104.2. |