2002-04-30 00:00:00THE PLANS DECLARE AN NFPA 13R DESIGN
 FIRE SPRINKLER SYSTEM.SEE FOOTNOTE
 {D} TO SBC TABLE 500.THERE FORE THE
 BUILDING IS REQUIRED TO BE ONE HOUR
 PROTECTED ORA COMPLETE 13 SYSTEM FOR
 THE THREE STORY REQUIREMENT.
  
 FURTHER, EGRESS WINDOWS, FIRE RATED
 CORRIDORS, AND ANY OTHER REDUCTIONS
 TAKEN FOR FIRE SPRINKLER SYSTEM ARE NOT
 APPLICABLE TO THIS BUILDING.SEE ALSO
 SBC 903.2.
  
 WHERE THE ROOF IS USED FOR EXIT ACCESS
 IT MUST COMPLY WITH SBC 1006.2 FOR
 SEPARATION FROM THE INTERIOR OF THE
 BUILDING.
  
 SHOW THE DETAILS FOR THE THIRD FLOOR
 EXTERIOR STAIR WITH REGARDS TO
 DIMENSIONS, DESIGN LOADS, HAND AND
 GUARD RAILS.SEE SBC 1007.
  
 THE PLANS DO NOT CLEARLY INDICATE THE
 FIRE RATED TENANT SEPARATION REQUIRED
 BY SBC 704.3.INCLUDING AT THE
 "CORRIDOR SIDE".
  
 DOES THE EXIT DISCHARGE ON THE WEST
 SIDECOMPLY WITH SBC 1010?
  
 SHEET A9.01.SHOW A SPECIFIC FRAMING
 DETAIL FOR THE SOFFIT CONSTRUCTION.
 HOW IS THE FIRE RATED SEPARATION
 BETWEEN FLOORS MAINTAINED?HOW IS THE
 MECHANICAL EQUIPMENT SUPPORTED AND
 ACCESSED?SEE SBC 104.2.