| 2002-04-30 00:00:00 | 1) MERCANTILE TENANT SPACES ARE TO BE | | | PROPERLY FIRE RATED FROM ONE ANOTHER BY | | | AT LEAST ONE HOUR. | | | 2) NOTES INDICATE ON PAGE A2.01 | | | INDICATES A 13R FIRE SPRINKLER SYSTEM. | | | THE MERCANTILE OCCUPANCIES MUST BE | | | PROTECTED IN ACCORDANCE WITH NFPA 13. | | | 3) THE EXISTING FIRE EXIT STAIR "TO BE | | | REMOVED OR REPLACED WITH COMPLYING | | | STAIRS". THE EXISTING STAIRWAY MUST | | | BE COMPLIANT WITH ALL OF THE | | | REQUIREMENTS FOR EXITING FROM THE | | | BUILDING AND FIRE CODES. THE STAIR | | | CANNOT BE REMOVED BECAUSE A DEAD-END | | | CONDITION IS EVIDENT. | | | 4) WITH REGARDS TO THE EXTERIOR STAIRS, | | | HOW IS EXIT DISCHARGE ACCOMPLISHED. | | | DOES EXITING OCCUR ON THE SAME PROPERTY, | | | SOMEONE ELSE'S PROPERTY, OR ALLEY. | | | PLEASE EXPLAIN. | | | 5) FIRE ALARM NOTES INDICATE CLASS B, | | | STYLE C CIRCUITS. ONLY CLASS A, STYLE D | | | CIRCUITS ARE ALLOWED. | | | 6) EXIT DOORS FOR THE MERCANTILE | | | OCCUPANCIES, DO THEY OPEN ONTO THE | | | SAME PROPERTY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|