Plan Review Notes
Plan Review Notes For Permit 01070273
Permit Number 01070273
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-04-30 00:00:001) MERCANTILE TENANT SPACES ARE TO BE
 PROPERLY FIRE RATED FROM ONE ANOTHER BY
 AT LEAST ONE HOUR.
 2) NOTES INDICATE ON PAGE A2.01
 INDICATES A 13R FIRE SPRINKLER SYSTEM.
 THE MERCANTILE OCCUPANCIES MUST BE
 PROTECTED IN ACCORDANCE WITH NFPA 13.
 3) THE EXISTING FIRE EXIT STAIR "TO BE
 REMOVED OR REPLACED WITH COMPLYING
 STAIRS". THE EXISTING STAIRWAY MUST
 BE COMPLIANT WITH ALL OF THE
 REQUIREMENTS FOR EXITING FROM THE
 BUILDING AND FIRE CODES. THE STAIR
 CANNOT BE REMOVED BECAUSE A DEAD-END
 CONDITION IS EVIDENT.
 4) WITH REGARDS TO THE EXTERIOR STAIRS,
 HOW IS EXIT DISCHARGE ACCOMPLISHED.
 DOES EXITING OCCUR ON THE SAME PROPERTY,
 SOMEONE ELSE'S PROPERTY, OR ALLEY.
 PLEASE EXPLAIN.
 5) FIRE ALARM NOTES INDICATE CLASS B,
 STYLE C CIRCUITS. ONLY CLASS A, STYLE D
 CIRCUITS ARE ALLOWED.
 6) EXIT DOORS FOR THE MERCANTILE
 OCCUPANCIES, DO THEY OPEN ONTO THE
 SAME PROPERTY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910