| Date |
Text |
| 2002-04-19 00:00:00 | ***************** UNSAT!**************** |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | AND MAKE NECESSARY CORRECTIONS AND |
| | RESUBMIT FOR REVIEW: |
| | |
| | 1} THERE ARE DISCREPANCIES IN THE TYPES |
| | OF UNITS LOCATED ON THE NORTH-WEST SIDE |
| | OF THE BUILDING.SHEET A2.02 INDICATES |
| | THE UNITS ARE TYPE"F"&"D",SHEET A2.03 |
| | INDICATES THEY ARE TYPES"C"&"F" AND |
| | E3.3 THEM AS"C"&"D".ALSO ON E3.3 THE"E" |
| | UNITS AREN'T LABELED. |
| | |
| | 2} THE METER CENTER MAIN #1 LOAD |
| | SUMMARY ON SHEET E6.1 LISTS ONLY 17 |
| | UNITS.PLEASE CLARIFY WHICH UNITS ARE |
| | NOT INCLUDED,LIST THEM AND PROVIDE LOAD |
| | CALCULATIONS ON THE SUMMARY SHEET FOR |
| | SAME. |
| | |
| | 3} ON SHEET E6.1,PANEL"LHP",CIRCUIT #'S |
| | 12-14,28-30,38-40 THE OCP IS INCORRECT |
| | FOR THE CONDUCTOR SIZE.THE"A"UNITS |
| | PANELS CIRCUIT#13-15 IS ALSO INCORRECT. |
| | |
| | 4} PANEL "LHP" CIRCUIT #36 DOES NOT |
| | CORRELATE TO SHEET E3.1 WHERE IT IS |
| | SHOWN SERVING THE HALL RECEPTACLE |
| | CIRCUIT. |
| | |
| | 5} THE HALL LIGHTING ON SHEET E2.1 NEEDS |
| | A 4-WAY SWITCH. |
| | |
| | 6} THE TYPE"B"UNITS ON SHEETS E2.2 & E2. |
| | 3 NEED A SMOKE DETECTOR IN BOTH BEDROOMS |
| | PER 2-2.1.1.1 NFPA-72 (1996). |
| | |
| | 7} CIRCUIT L2-14 IN THE LAUNDRY ROOM |
| | SHEET E3.2 IS MISMARKED. |
| | |
| | 8} SHEET E2.2 UNIT"D"HAS NO SMOKE |
| | DETECTRS IN THE STUDY,IF IT IS INTENDED |
| | AS A SLEEPING ROOM IT MUST COMPLY WITH |
| | 2-2.1.1.1 AS THE 3RD FLOOR UNIT DOES. |
| | |
| | 9} PLEASE NOTE THE LOCATION OF THE SMOKE |
| | DETECTORS IN UNIT TYPES"A","C"&"E" WITH |
| | RESPECT TO THE KITCHENS IN THESE UNITS. |
| | IF THESE WERE MOVED FURTHER FROM THE |
| | KITCHEN, ESPECIALLY GIVEN THE FACT OF |
| | THE DROPPED SOFFITS,IT COULD HELP |
| | REDUCE THE THE PROBABILITY OF NUISANCE |
| | ALARMS. |
| | |
| | 10} PLEASE VERIFY THE DIMENSIONS OF THE |
| | MECHANICAL ROOM. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/659/8096 EXT. 8392 |