| Plan Review Notes For Permit 01070198 |
| Permit Number |
01070198 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-24 00:00:00 | 1) ELECTRONIC SWITCHES WILL BE REQUIRED | | | ON THE O.S.& Y VALVES. | | | 2) SINCE THE BUILDING IS A HIGH-RISE | | | BUILDING, TWO FIRE DEPARTMENT | | | CONNECTIONS WILL BE REQUIRED. NO FIRE | | | HYDRANTS SHOWN ON PLANS. ACCORDING TO | | | EVAN ROSENBLATT OF SUFFOLK, FIRE | | | HYDRANTS ARE LOCATED ON THE NORTH | | | SIDE OF THE BUILING. HE WAS ADVISED THAT | | | THE FDC'S ARE TO BE WITHIN 150 FEET OF | | | FIRE HYDRANTS. | | | ACCORDING TO MR. ROSENBLATT, NO GAS | | | SERVICE WILL BE PROVIDED. | | | 3) PLEASE BE ADVISED THAT 50 PERCENT | | | OF THE EXITS ARE REQUIRED TO DISCHARGE | | | DIRECTLY TO THE EXTERIOR EXCLUSIVE OF | | | HORIZONTAL EXITS. | | | 4) A TEMPORARY STANDPIPE WILL BE | | | REQUIRED FOR THE BUILDING WHEN IS IS | | | UNDER CONSTRUCTION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|