| 2001-10-04 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY. |
| | |
| | THE CRAVEN THOMPSON CIVIL PLANS TITLE |
| | SHEET CALLS OUT AN ADDRESS OF 915 S |
| | DIXIE HWY.WHY? |
| | |
| | THE PLANS ARE MOSTLY INCOMPLETE AND A |
| | CLOSE AND CRITICAL PLAN REVIEW FOR CODE |
| | COMPLIANCE IS NOT POSSIBLE. IS THE |
| | DESIGN OF THIS BUILDING COMPLETED YET? |
| | |
| | |
| | PROVIDE ADDITIONAL INFORMATION ON THE |
| | WATERPROOFING METHODS. SEE SBC 1814.2 |
| | WHAT IS A "MUD BED" ? |
| | |
| | THE LOBBY LEVEL IS SHOWN AT 11.0' NGVD |
| | AND THE 1ST PARKING LEVEL AT 13'-10". |
| | PLEASE CLARIFY THE DESIGN INTENT. |
| | ALSO REVIEW THE HC CODE FOR PARKING |
| | GARAGE CLEAR HEIGHT. |
| | |
| | DIMENSIONS TO LOCATE THE COLUMNS ON |
| | SHEET S-01, OR OTHERS, ARE NOT READILY |
| | DISCERNIBLE. |
| | |
| | IS THERE MORE DESCRIPTIVE DETAIL |
| | AVAILABLE FOR THE STRUCTURAL COMPONENTS |
| | SHOWN ASW-1, W-1A AND W-2? |
| | |
| | SHEET S-01 GRID LINE 4 SHOWS THE 15 DEG |
| | ANGLE COMMENCING AT AN INDETERMINATE |
| | POINT. |
| | |
| | THE RWDI TEST REPORT REFERENCES ASCE |
| | 7-93.SBC 97 INVOKES ASCE 7-95. |
| | |
| | WHAT RECOGNIZED ACCREDITATIONS DOES THE |
| | WIND TUNNEL TESTING FACILITY HAVE? |
| | |
| | THE THRESHOLD INSPECTION PLAN REFERENCES |
| | THE SOUTH FLORIDA BUILDING CODE ON PAGE |
| | 3.PLEASE CHANGE OR REVISE TO INCLUDE |
| | THE 1997 STANDARD BUILDING CODE, SBCCI. |
| | |
| | PLEASE DEMONSTRATE COMPLIANCE WITH SBC |
| | 1803.2 FOR THE ADJOINING PROPERTY |
| | |
| | SKETCHES IN THE RWDI REPORT INDICATE |
| | THERE MAY BE TABLE 600 CONFLICTS WITH |
| | THE WALL OPENINGS, AND THE STAIR |
| | LOCATIONS MAY NOT MEET THE 1/2 DIAGONAL |
| | DISTANCE REQUIREMENT OF SBC 1004.1.4. |
| | |
| | ON THRESHOLD BUILDINGS, 3 SETS OF PLANS |
| | AND INFORMATION ARE REQUIRED. |
| | |
| | GIVEN THE 100% LOT COVERAGE, HAS THE |
| | MOBILIZATION AND LOCATION OF MATERIALS |
| | AND EQUIPMENT BEEN ADDRESSED?CONTACT |
| | THE CITY ENGINEER AT 659-8040 FOR USE |
| | OF PUBLIC RIGHT OF WAY INCLUDING THE |
| | PLACEMENT OF THE OIL INTERCEPTOR SHOWN |
| | ON SHEET P-1. |
| | |
| | HOW WILL ELECTRICAL POWER BE DELIVERED |
| | TO THE SUMP PUMPS SHOWN ON SHEET P-1 |
| | |
| | WHERE IS THE PERMIT APPLICATION, AND ITS |
| | ATTENDANT PLANS, FOR THE BUILDING |
| | PROPER?SEE SBC 104.4.3. |
| | |
| | BEFORE ANY PERMITS TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PERMIT PLANS STAMPED |
| | BYTHAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICTION. |