| Plan Review Notes For Permit 01070198 |
| Permit Number |
01070198 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-09 00:00:00 | 1) NO UNDEGROUND UTILITIES SHOWN | | | ON DRAWINGS. ARE GAS, ELECTRIC, WATER, | | | SEWER, OR FIRE PROTECTION LINES PRESENT. | | | 2) NO FIRE HYDRANTS SHOWN ON THE | | | DRAWINGS. | | | 3) WHERE ARE FUTURE CONNECTIONS TO | | | THE CITY WATER SUPPLY FOR FIRE | | | PROTECTION TO BE MADE. | | | 4) COULD NOT LOCATE FIRE PUMP OR | | | LOCATION OF PROPOSES FIRE PUMP. WHERE | | | WILL THE FIRE PROTECTION SERVICE ENTER | | | THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|