Plan Review Notes
Plan Review Notes For Permit 01070183
Permit Number 01070183
Review Stop E
Sequence Number 1
Notes
Date Text
2001-07-10 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NO LOAD CALCU-
 -LATIONS WERE SUBMITTED WITH ALL NEW
 LOADS? PLEASE SUBMIT WITH ALL NEW
 LOADS WITH EXISTING LOADS AND SHOW SIZE
 OF EXISTING SERVICE.
  
 2)NOTE: PLEASE NOTE THAT SPEC SHEET
 SUBMITTED SHOWS MAX FUSE SIZE AT 40AMPS
 AND PLANS SHOWS FUSED AT 50AMPS.
 PLEASE CLARIFY AND CORRELATE.
  
 PLEASE SUBBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372