| 2001-07-23 00:00:00 | DENIED; |
| | |
| | 1.PAGE A-1 PUBLIC RESTROOMS; SHOW TURN- |
| | ING CIRCLE. |
| | 2.SHOW COMPLIANCE TO 94 SPC TABLE 407. |
| | MINIMUM BATHROOM FACILITIES. |
| | 3.PAGE P-1 NOTE 7 MECHANICAL WATER |
| | HAMMER ARRESTERS SHALL COMPLY WITH |
| | SPC SEC 607.8.2 AND INSTALLED PER |
| | MANUFACTOR'S SPECIFCATIONS. |
| | 4.WASHING MACHINES SHALL NOTE CONNECT |
| | TO A 2" CROSS. SEC. 409.12.3 RECOMMEND |
| | 3" PIPE. |
| | 5.FLOOR DRAINS REQUIRED IN LAUNDRY ROOM |
| | WITH TRAP PRIMERS. |
| | 6.PAGE P-4 NOTE 19 FIRE PROTECTION. |
| | PLEASE SUBMIT MANUFACTORS SPECIFICA- |
| | TIONS AND GIVE UL LISTING NUMBER. |
| | 7.SHOW DOMESTIC WATER RISER. |
| | 8.SHOW ROOF DRAIN RISER DIAGRAM. |
| | 9.PAGE A-8 ROOF DRAINS. CALCULATE SQUARE |
| | FOOTAGE FOR EACH DRAIN AND SIZE PIPE |
| | PER CHAPTER 11. |
| | 10.SHOW WATER PIPE ON P-2 AND 3. |
| | 11.SITE PLAN GIVES NO INFORMATION. |
| | A.SHOW WATER LOCATION AND SIZE |
| | SHOW BACKFLOW. |
| | B.SEWER WHERE AND WHAT SIZE? |
| | C.STORM WHERE DOES RAIN WATER GO? |
| | |
| | FAIR HOUSING ACT NOTES; |
| | 1.SPECIFY ON DRAWING IF PLANS ARE TO |
| | COMPLY WITH SPECIFICATION "A" OR "B". |
| | 2.DOOR OPENINGS TO BATHROOMS MUST HAVE |
| | A CLEAR DOOR OPENING OFV 32". |
| | 3.SHOW CLEAR FLOOR SPACE FOR BATHROOM |
| | FIXTURES AND KITCHEN APPLIACES. |
| | 4.SHOW REINFORCED WALLS FOR LATER |
| | INSTALLATION OF GRAB BARS. |
| | 5.UNIT A PAGE A-4 WHAT IS THE DIMENSION |
| | BETWEEN CABINETS IN KITCHEN. SEE SEC. |
| | 7.9. |
| | 6.UNIT D BATHROOM DOES NOT COMPLY WITH |
| | FHA REQUIREMENTS. SEE EXAMPLE B PAGE |
| | 7.36. ALSO KITCHEN SINK, AN ADAPTIBLE |
| | CABINET WILL BE REQUIRED SINCE THERE |
| | IS NOT ENOUGH ROOM FOR A PARALLEL |
| | APPROACH. PLEASE SHOW DETAIL. |
| | 7.UNIT B DOES NOT COMPLY. SEE EXAMPLE B |
| | PAGE 7.37. |
| | 8.UNIT H SAME AS B SEE PLAN REVIEW NOTE |
| | 7. |
| | 9.SHOW DETAIL OF TOILET. WHAT SIDE IS |
| | 18"S AND A TOTAL OF 33"S CLEARANCE. |
| | SEE FHA 7.43 |
| | 10.IF UNIT G IS AN OFFICE BATHROOM AND |
| | KITCHEN SHALL COMPLY WITH FACBC IF |
| | IT WILL BE A MANAGERS APT. IT SHALL |
| | COMPLY WITH FHA REQUIREMENTS. |
| | 11.LAUNDRY ROOMS SHALL COMPLY WITH FHA |
| | 2.26. |
| | |
| | PLUMBING PLAN REVIEW NOTES BY; |
| | JOHN LEECH |
| | 659-8096 EXT.8369 |