Plan Review Notes
Plan Review Notes For Permit 01070180
Permit Number 01070180
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-07-05 00:00:001) FIRE HYDRANT LOCATIONS NOT SHOWN ON
 SITE PLAN. WHERE IS BACKFLOW DEVICE.
 2) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS. PLEASE BE ADVISED THAT FS 553.895
 REQUIRES ANY BUILDING THREE OR MORE
 STORIES IN HEIGHT REGARDLESS OF
 OCCUPANCY BE PROVIDED WITH AN AUTOMATIC
 FIRE SPRINKLER SYSTEM.
 3) PLEASE PROVIDE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM
 INSTALLATION. FIRE ALARM SYSTEM TO BE
 CLASS A OR FULLY ADDRESSABLE. CUT
 SHEETS, WIRING DIAGRAMS AND BATTERY
 CALCULATIONS ARE TO BE PROVIDED.
 4) SMOKE DETECTORS WITHIN APARTMENTS
 ARE TO BE ELECTRICAL AND BE LOCATED
 NO CLOSER THAN 3 FEET AWAY FROM
 AIR CONDITIONER DIFFUSERS.
 5) SEPARATE PERMIT REQUIRED FOR FIRE
 ALARM INSTALLATION.
 6) EXIT DOORS INTO STAIRWELLS SHOULD
 SWING IN THE DIRECTION OF EXIT TRAVEL.
 7) STAIR TREADS ARE TO BE AT LEAST 11"
 AS REQUIRED BY THE LIFE SAFETY CODE,
 1985 EDITION.
 8) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS OF THE BUILDING.
 9) STAIRWELL DOORS ARE TO BE AT LEAST
 C LABELED (45 MINUTE) FIRE DOORS
 WITH CLOSERS.
 10) ALL RATED FIRE DOORS ARE TO BE
 INSTALLED IN FIRE RATED FRAMES AND
 BE EQUIPPED WITH SELF-CLOSING DEVICES
 THAT CAUSE THE DOORS TO LATCH.
 11) CLEARLY IDENTIFY ALL FIRE RATED
 SEPARATIONS BETWEEN TENANTS, PARKING,
 ETC.
 12) PLEASE IDENTIFY FIRE EXTINGUISHER
 LOCATIONS WITHIN BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910