| 2001-07-05 00:00:00 | 1) FIRE HYDRANT LOCATIONS NOT SHOWN ON |
| | SITE PLAN. WHERE IS BACKFLOW DEVICE. |
| | 2) NO FIRE SPRINKLER DRAWINGS OR |
| | HYDRAULIC CALCULATIONS PROVIDED WITH |
| | PLANS. PLEASE BE ADVISED THAT FS 553.895 |
| | REQUIRES ANY BUILDING THREE OR MORE |
| | STORIES IN HEIGHT REGARDLESS OF |
| | OCCUPANCY BE PROVIDED WITH AN AUTOMATIC |
| | FIRE SPRINKLER SYSTEM. |
| | 3) PLEASE PROVIDE FIRE ALARM SYSTEM |
| | SHOP DRAWINGS FOR FIRE ALARM |
| | INSTALLATION. FIRE ALARM SYSTEM TO BE |
| | CLASS A OR FULLY ADDRESSABLE. CUT |
| | SHEETS, WIRING DIAGRAMS AND BATTERY |
| | CALCULATIONS ARE TO BE PROVIDED. |
| | 4) SMOKE DETECTORS WITHIN APARTMENTS |
| | ARE TO BE ELECTRICAL AND BE LOCATED |
| | NO CLOSER THAN 3 FEET AWAY FROM |
| | AIR CONDITIONER DIFFUSERS. |
| | 5) SEPARATE PERMIT REQUIRED FOR FIRE |
| | ALARM INSTALLATION. |
| | 6) EXIT DOORS INTO STAIRWELLS SHOULD |
| | SWING IN THE DIRECTION OF EXIT TRAVEL. |
| | 7) STAIR TREADS ARE TO BE AT LEAST 11" |
| | AS REQUIRED BY THE LIFE SAFETY CODE, |
| | 1985 EDITION. |
| | 8) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS OF THE BUILDING. |
| | 9) STAIRWELL DOORS ARE TO BE AT LEAST |
| | C LABELED (45 MINUTE) FIRE DOORS |
| | WITH CLOSERS. |
| | 10) ALL RATED FIRE DOORS ARE TO BE |
| | INSTALLED IN FIRE RATED FRAMES AND |
| | BE EQUIPPED WITH SELF-CLOSING DEVICES |
| | THAT CAUSE THE DOORS TO LATCH. |
| | 11) CLEARLY IDENTIFY ALL FIRE RATED |
| | SEPARATIONS BETWEEN TENANTS, PARKING, |
| | ETC. |
| | 12) PLEASE IDENTIFY FIRE EXTINGUISHER |
| | LOCATIONS WITHIN BUILDING. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |