Plan Review Notes
Plan Review Notes For Permit 01070180
Permit Number 01070180
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SIGNED, DATED, SEALED PER FS/FAC
 471.025.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL.
 PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372