| Plan Review Notes For Permit 01070176 |
| Permit Number |
01070176 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-24 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | | | | IS DUCTWORK BEING REPLACED, ADDED TO | | | MODIFIED?PROVIDE DUCT SIZE. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | REQUIRED AS PER 1997 SMC 406 WITH | | | NOTIFICATION TO ALARM/STROBE AS PER | | | NFPA 90A 4-4.4.3. | | | | | | NOTE:PRIOR TO CONNECTING TO ANY | | | EXISTING DUCTWORK, PLEASE CALL | | | FOR AN INSPECTION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|