2001-08-21 00:00:00*******************PROVISO**************
  
  
 FIRE DAMPERS REQUIRED ON EXHAUST
 DUCTWORK PENETRATING FIRE RATED WALLS
 IN FILE ROOMS.PLEASE SUBMIT REVISED
 PLAN INDICATING FIRE DAMPERS FOR THESE
 PENTRATIONS.NOTE:DUCTWORK SHALL
 PENETRATE RATED WALL PERPENDICULAR SO
 FIRE DAMPER CAN BE INSTALLED PROPERLY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.