2001-07-26 00:00:00*******************DENIED***************
  
  
 HP-9, SUPPLY DUCTS FOR ROOMS MF12 AND
 EC6 REQUIRE FIRE DAMPERS WHERE DUCT
 PENETRATES THE FIRE RATED WALL.
  
 PLEASE PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2.
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8333.