| 2001-07-25 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01070173 |
| | CONT: CATALFUMO |
| | TEL: (561) 694-3000 X 256 |
| | ARCH: ADA |
| | TEL: (561) 626-7381 |
| | |
| | 1)- STAIRWELL DOOR #2 SBC 4.12.8.1 EXITS |
| | ALL STAIRWELL DOORS WHICH ARE TO BE LOCK |
| | ED FROM THE STAIRWELL SIDE SHALL HAVE |
| | THE CAPACITY OF BEING UNLOCK SIMULTAN- |
| | EOUSLY WITHOUT UNLATCHING UPON A SIGNAL |
| | FROM THE CENTRAL CONTROL STATION. THE |
| | DOORS SHALL BE SIMILARLY UNLOCKED UPON |
| | ACTUATION OF THE SPRINKLER SYSTEM OR |
| | UPON POWER FAILURE. |
| | 2)- COMMON CORRIDORS A & B SBC 704.2.1.4 |
| | FIRE REATED WALLS, WALLS THAT REQUIRE |
| | PROTECTED OPENINGS SHALL HAVE SIGNAGE, |
| | " FIRE & SMOKE BARRIER PROTECT ALL OPEN- |
| | INGS". |
| | 3)- SBC 609.2.1 TYPE I & TYPE II BUILD- |
| | INGS PARTITIONS SHALL BE CONSTRUCTED OF |
| | NONCOMBUSTIBLE MATERIAL, FIRE TREATED |
| | WOOD, ALL BACKING,BUCKS ETC |
| | 4)- SBC 104.2.2* ADD INFORMATION |
| | REQUIRED: SHEET A-2 DETAIL 14 AND A-3 |
| | DETAIL 4, SOFFITS ANCHORAGE TO CONCRETE |
| | DECK ABOVE,SPACING & TYPE OF ANCHOR? |
| | 5)- SBC 1204.2 THE WALLS AND FLOOR OF |
| | ALL RESTROOMS SHALL BE LINED WITH NON- |
| | ABSORBANT MATERIALS TO A HEIGHT OF 4'-0" |
| | 6)- PROGRAM SPECIALIST VI FL. ACCESSIBIL |
| | ITY CODE 1997: 4.13.6 MANEUVERING |
| | CLEARENCES AT DOORS REQUIRES A MINIMUM |
| | OF 18" SIDE WALL SPACE ON THE LATCH |
| | SIDE OF THE DOOR. |
| | 7)- FL ACC CODE 4.5.1 FLOOR SURFACES |
| | ALONG ACCESSIBLE ROUTES AND IN ACCESS- |
| | IBLE ROOMS & SPACES INCLUDING FLOORS, |
| | WALKS, RAMPS & STAIRS SHALLBE FIRM & |
| | SLIP RESISTANT. ADDAAG A-5: A SLIP |
| | COEFFICIENT OF 0.6 IS RECCOMENDED FOR |
| | ACCESSIBLE ROUTES & 0.8 FOR RAMPS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |