| 2002-02-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 - FHA AMEND-98 |
| | DESIGN MANUAL |
| | |
| | 1) SHT T1.01 COVER SHEET CALLS FOR IRR- |
| | AGATION SHEETS IR-1/IR-2, NONE FOUND. |
| | PLEASE SUBMIT IRRIGATION SHEETS. |
| | 2) SHT 10.01 GENERAL NOTES #2 CHANGE |
| | CODE REFERENCE TO READ FLA. BLDG. CODE |
| | 2001. |
| | 3) SHT P-2 1ST FLOOR/1ST FLOOR (REV),"A" |
| | CLEANOUT REQUIRED AT CHANGE OF DIRECTION |
| | GREATER THAN 45 DEGREES. FBC SEC 708.3.3 |
| | 4) SHT P-2 2ND FLOOR/2ND FLOOR (REV),"A" |
| | MINIMUM 1-1/2" WASTE ARM TO KITCHEN SINK |
| | NOT 1" AS SHOWN. FBC TABLE 709.1 |
| | 5) SHT P-3 1ST FLOOR/1ST FLOOR (REV),"B" |
| | CLEANOUT REQUIRED AT CHANGE OF DIRECTION |
| | GREATER THAN 45 DEGREES. FBC SEC 708.3.3 |
| | 6) SHT P-3 2ND FLOOR/2ND FLOOR (REV),"B" |
| | MINIMUM 1-1/2" WASTE ARM TO KITCHEN SINK |
| | NOT 1" AS SHOWN. FBC TABLE 709.1 |
| | 7) SHT P-6 WATER RISER DIAGRAMS TYPICAL |
| | FOR ALL UNITS. WATER HAMMER ARRESTORS |
| | SHALL BE LOCATED IN AN "EFFECTIVE RANGE" |
| | OF ALL QUICK CLOSING VALVES (SOLENOID) |
| | PLEASE SHOW THESE ON RISER DIAGRAMS. |
| | FBC SEC 604.9 |
| | 8) SHT P-6 WATER RISER DIAGRAM FOR "C" |
| | UNIT SHOWS AIR CHAMBER. AIR CHAMBERS ARE |
| | NOT APPROVED, PLEASE REMOVE. |
| | 9) SHT P-6 SANITARY RISER DIAGRAM. W/M |
| | STACK SHOWS 2" ON HORIZONTAL DRAIN LINE |
| | BUT 3" ON VERTICAL STACK. PLEASE SIZE |
| | DRAIN FOR 3" ALSO. |
| | 10) PER NEIL MELICK APPLICATION FOR FBC |
| | WILL HAVE TO BE SUBMITTED. PREVIOUS |
| | APPLICATION SHALL BE VOIDED. |
| | |
| | REVIEW BY KEN STEVENS |