| 2002-01-30 00:00:00 | THE BUILDING WAS REVIEWED UNDER THE | | | FLORIDA FIRE PREVENTION CODE. | | | 1) FIRE HYDRANTS WILL BE RELOCATED TO | | | ISLANDS TO PREVENT PROBLEMS WITH ACCESS | | | TO THEM. THIS ARRANGEMENT WAS AGREED TO | | | BY MR. FELIX SIERRA | | | 2) GENERAL NOTES SECTION SHOULD READ | | | FLORIDA FIRE PREVENTION CODE. | | | 3) ALL STORAGE ROOMS OUTSIDE OF | | | DWELLING UNITS TO BE PROTECTED BY AT | | | LEAST ONE HOUR FIRE SEPARATION OR FIRE | | | SPRINKLERS. | | | 4) THE REQUIREMENT FOR A FIRE ALARM | | | SYSTEM STILL SEEMS TO BE PRESENT. THE | | | TWO EXCEPTIONS TO THIS CODE REQUIREMENT | | | DOES NOT APPEAR TO APPLY. PLEASE REVIEW | | | CODE REQUIREMENT AND EXCEPTIONS. | | | 5) THE INFORMATION PROVIDED FOR THE | | | WINDOWS IS CONFUSING. ARE THE EGRESS | | | WINDOWS, SELF-CLOSING. PLEASE PROVIDE | | | ADDITIONAL DETAILS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|