| 2001-12-10 00:00:00 | THE TRUSS LAYOUT STILL CALLS OUT THE |
| | ASCE 7-93 AND THE ENGINEERING SHEETS |
| | ARE NOT SPECIFIC.THIS CAN BE |
| | ADDRESSED SUBSEQUENT TO PERMITTING AND |
| | PRIOR TO INSTALLATION. |
| | |
| | THE ENTRANCE DOORS TO THE UNITS ARE |
| | REQUIRED TO BE FIRE RATED BY SBC |
| | 1006.2.4, BOTH THE UPPER AND LOWER |
| | UNITSARE SUBJECT TO THIS REQUIREMENT. |
| | THIS WAS REQUESTED ON THE PREVIOUS |
| | CHECKLIST. ALSO, THE WINDOWS IN THE "TEN |
| | FEET WIDE SHADOW"SEE THE ATTACHED |
| | COPY OF THE SBC CODE COMMENTARY. |
| | |
| | |
| | THE "CHASE" ON SHEET 6/A7.03 MUST |
| | COMPLY WITH SBC 705.6.1.2 WITH REGARDS |
| | TO THE DRYER, EXHAUST DUCTS, PLUMBING |
| | ,ELECTRICAL AND ANY OTHER MATERIALS |
| | PENETRATING RATED WALLS OR FLOORS AND |
| | NOT CONTAINED IN A FIRE RATED SHAFT. |
| | |
| | THERE ARE NO ARCHITECTURAL SITE PLANS |
| | OR PROPERTY SURVEY(S),OR FINISHED FLOOR |
| | ELEVATIONS RELATIVE TO NGVD. |
| | |
| | THE SKETCHES DATED 11/7/01 BY J. |
| | FERNANDEZ-BARQUIN, PE, INVESTIGATE THE |
| | HAND AND GUARD RAILS UNDER ONLY ONE |
| | CONDITION.AN ANALYSIS WAS NOT |
| | REQUESTED BUT A THE DESIGN LOADS TO BE |
| | USED IN ACCORDANCE WITH SBC 1608.2. |
| | ATTACHED IS AN EXERPT FROM THE SBC CODE |
| | COMMENTARY DEPICTING THE LOADS AND |
| | THEIR APPLICATION. |
| | |
| | THIS PROJECT WILL APPARENTLY HAVE 24 |
| | BUILDINGS IN TWO SEPARATE LOCATIONS. |
| | AS NOTED IN THE FIRST PLAN REVIEW, |
| | SEPARATE PERMITS ARE REQUIRED FOR EACH |
| | BUILDING.WHAT IS BEING APPLIED FOR |
| | WITH THIS APPLICATION? |