| 2001-10-29 00:00:00 | THE LETTER DATED 8/20/01 FROM JUAN |
| | FERNANDEZ-BARQUIN, P.E. CALLS OUT WIND |
| | DESIGN TO ASCE 7-88/93.THE 1997 |
| | STANDARD BUILDING CODE INVOKES ASCE |
| | 7-95.PLEASE REVISE AS NECESSARY AND |
| | DEMONSTRATE COMPLIANCE WITH SAME.WEST |
| | PALM BEACH IS IN A 140 MPH ZONE FOR ASCE |
| | AND 110 MPH IF SBC 1606.2 IS USED.SEE |
| | SBC 1606.2.2 RE: MIXING OF WIND |
| | PRESSURES FROM DIFFERENT SOURCES. SHEET |
| | S11 WRONGLY CITES 100 MPH AND ASCE 7-93. |
| | MARTINEZ TRUSSES USED ASCE 7-93 AS WELL. |
| | |
| | |
| | THE NOA FOR THE METAL TECH SHUTTERS |
| | EXPIRED 10/01/01.FURTHER, THE |
| | COMPONENTS ARE NOT MARKED AS PROVIDED |
| | FOR IN SECTION 6.1.2 OF THAT REPORT OR |
| | AN INSTALLATION SCHEDULE INCLUDED. |
| | |
| | SEE THE BUILDING OFFICIAL'S |
| | INTERPRETATION OF HURRICANE MISSILE |
| | IMPACT REGARDING THE USE OF SHUTTERS ON |
| | MULTI FAMILY BUILDINGS.A COPY IS |
| | ATTACHED. |
| | |
| | THE ENTRANCE DOORS TO THE UNITS ARE |
| | REQUIRED TO BE PROTECTED OPENINGS AS |
| | PROVIDED FOR IN SBC 1006.2.4. THIS IS |
| | NOT READILY DISCERNIBLE FROM THE DOOR |
| | SCHEDULE ON SHEET A5.01.ALSO, THE |
| | WINDOW TYPE [C] IS SHOWN AS AN OPERABLE |
| | WINDOW.THIS MUST BE A TESTED FIRE |
| | RATED ASSEMBLY.SEESBC 705.1.3.THE |
| | WINDOWS SHOWN AS [H] AND THE GLASS BLOCK |
| | IN THE END "C" UNITS ARE SUBJECT TO |
| | SBC1006.2.4. |
| | |
| | SHOW THE FIRE DESIGN NUMBER FOR THE 1 HR |
| | SHAFT IN SECTION 6/A7.03.SEE SBC |
| | 701.2. |
| | |
| | PLEASE PROVIDE A DIMENSIONED SITE PLAN |
| | AND A RECENT PROPERTY SURVEY. |
| | |
| | SHOW THE FINISH FLOOR ELEVATIONS |
| | RELATIVE TO NGVD. |
| | |
| | SHOW THE HANDRAIL AND GUARDRAIL LOADS AS |
| | REQUESTED ON THE PREVIOUS CHECKLIST, |
| | SEE SBC 1608.2. |
| | |
| | EACH BUILDING REQUIRES A SEPARTE PERMIT, |
| | ALSO SEE THE PREVIOUS LIST REGARDING IM |
| | PACT FEES AND A RESIDENT INSPECTOR. |