| 2001-08-07 00:00:00 | *******************DENIED*************** |
| | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW: |
| | |
| | 1.PLAN SHEET M-4, DRYER EXHAUST VENTS |
| | ARE GREATER THAN 25'.AS PER 1997 |
| | SMC 509.3, THE MAXIMUM LENGTH SHALL |
| | NOT EXCEED 25' FROM DRYER LOCATION |
| | TO WALL OR ROOF CAP.5' REDUCTION |
| | FOR EACH 90 DEGREE BEND AND 2 1/2' |
| | REDUCTION FOR EACH 45 DEGREE BEND. |
| | THE WALL OR ROOF CAP SHALL BE NON- |
| | SCREENED WITH BACK DRAFT DAMPER. |
| | |
| | 2.PLAN SHEET M-6, A/C & E.W.H. DETAIL, |
| | AS PER AMENDED 1994 SPC 804.3 #5., |
| | CONDENSATE DRAINS SHALL VENT TO THE |
| | ATMOSHERE AND NOT TERMINATE IN THE |
| | THE WALL AS SHOWN ON THE DETAIL. |
| | SHOULD VENT TERMINATE IN THE ATTIC, |
| | IS SHALL BE A MINIMUM OF 6" ABOVE |
| | THE INSULATION. |
| | |
| | 3.PLAN SHEET M-6, A/C & E.W.H. DETAIL, |
| | INDICATES OVERFLOW PROTECTION SHALL |
| | BE ON THE UPPER FLOORS ONLY.THIS |
| | IS UNACCEPTABLE, OVERFLOW PROTECTION |
| | SHALL BE ON ALL UNITS TO PREVENT |
| | DAMAGE TO CARPET, WALLS AND INTERIOR |
| | OF APPARTMENT. |
| | |
| | NOTE:HEIGHT REQUIREMENTS FOR CONTROLS |
| | SHALL COMPLY WITH CHAPTER 5 OF |
| | FAIR HOUSING ACT. |
| | |